Carrier AQUAFORCE 30XA080-500 User Manual

Page 54

Advertising
background image

54

Table 3 — 30XA Minimum and Maximum Cooler Flow Rates

* For applications requiring cooler leaving water temperature operation at less than

40 F (4.4 C), the units require the use of antifreeze and application may require
one of the special order brine option. Contact your local Carrier representative for
more information.

† For applications requiring cooler entering water temperature operation at less than

45 F (7.2 C), contact your local Carrier representative for unit selection using the
Carrier electronic catalog.

NOTE: Nominal flow rates required at ARI (Air Conditioning and Refrigeration
Institute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering
water temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft

2

-hr-F/Btu

(0.000018 m

2

-K/kW).

ITEM

MINIMUM

MAXIMUM

NOMINAL

Cooler Leaving Water Temperature*

40 F (4.4 C)

60 F (15 C)

Cooler Entering Water Temperature†

45 F (7.2 C)

70 F (21.1 C)

30XA

UNIT SIZE

Cooler

Number of

Passes

Minimum Flow Rate

Maximum Flow Rate

Nominal Flow Rate

(gpm)

(L/s)

(gpm)

(L/s)

(gpm)

(L/s)

080

Standard

2

95

6.0

379

23.9

180.4

11.4

Plus one pass

3

43

2.7

192

12.1

Minus one pass

1

196

12.4

782

49.3

090

Standard

2

101

6.4

403

25.4

201.9

12.7

Plus one pass

3

43

2.7

200

12.6

Minus one pass

1

229

14.4

917

57.9

100

Standard

2

101

6.4

403

25.4

225.5

14.2

Plus one pass

3

43

2.7

200

12.6

Minus one pass

1

229

14.4

917

57.9

110

Standard

2

125

7.9

501

31.6

244.9

15.5

Plus one pass

3

61

3.8

244

15.4

Minus one pass

1

254

16.0

1014

64.0

120

Standard

2

125

7.9

501

31.6

264.8

16.7

Plus one pass

3

73

4.6

293

18.5

Minus one pass

1

281

17.7

1124

70.9

140

Standard

2

134

8.5

538

33.9

317.8

20.1

Plus one pass

3

73

4.6

293

18.5

Minus one pass

1

324

20.4

1296

81.8

160

Standard

2

165

10.4

660

41.6

365.1

23.0

Plus one pass

3

98

6.2

391

24.7

Minus one pass

1

354

22.3

1418

89.5

180

Standard

2

202

12.7

807

50.9

409.6

25.8

Plus one pass

3

73

4.6

391

24.7

Minus one pass

1

416

26.2

1662

104.9

200

Standard

2

223

14.1

892

56.3

463.9

29.3

Plus one pass

3

98

6.2

391

24.7

Minus one pass

1

458

28.9

1833

115.6

220

Standard

2

235

14.8

941

59.4

505.9

31.9

Plus one pass

3

122

7.7

489

30.9

Minus one pass

1

501

31.6

2004

126.4

240

Standard

2

266

16.8

1063

67.1

545.8

34.4

Plus one pass

3

147

9.3

587

37.0

Minus one pass

1

538

33.9

2151

135.7

260

Standard

2

257

16.2

1027

64.8

600.3

37.9

Plus one pass

3

141

8.9

562

35.5

Minus one pass

1

584

36.8

2334

147.3

280

Standard

2

293

18.5

1173

74.0

642.2

40.5

Plus one pass

3

141

8.9

562

35.5

Minus one pass

1

620

39.1

2481

156.5

300

Standard

2

327

20.6

1308

82.5

687.5

43.4

Plus one pass

3

174

11.0

697

44.0

Minus one pass

1

687

43.3

2750

173.5

325

Standard

2

361

22.8

1442

91.0

733.4

46.3

Plus one pass

3

211

13.3

843

53.2

Minus one pass

1

724

45.7

2897

182.8

350

Standard

2

379

23.9

1516

95.6

775.4

48.9

Plus one pass

3

244

15.4

978

61.7

Minus one pass

1

767

48.4

3068

193.6

400

Standard

1

501

31.6

2004

126.4

917.6

57.9

Plus one pass

Minus one pass

450

Standard

1

501

2004

1019.3

64.3

Plus one pass

Minus one pass

500

Standard

1

501

2004

1092.8

68.9

Plus one pass

Minus one pass

Advertising