Carrier AQUAFORCE 30XA080-500 User Manual

Page 53

Advertising
background image

53

COOLER PUMP CONTROL — It is required that cooler

pump control be utilized on all chillers unless the chilled water

pump runs continuously or the chilled water system contains a

suitable antifreeze solution. Control of dual external pumps re-

quires installation of the external pump control accessory pack-

age (Part No. 00EFN900003200A).

If cooler pump control is not utilized, it is required that the

chiller be electrically interlocked with the chilled water pump

starter. The interlock should be wired to terminals TB5-1 and

TB5-2. It is also required that the cooler pump output be used

as an override to the chilled water pump control circuit to pro-

vide additional freeze protection.

Refer the control and power wiring schematic on page 63

for proper connection of the cooler pump output. The cooler

pump output will remain energized for 30 seconds after all

compressors stop due to an OFF command. In the event a

freeze protection alarm is generated, the cooler pump output

will be energized regardless of the cooler pump control soft-

ware configuration. The cooler pump output is also energized

anytime a compressor is started and when certain alarms are

generated. A thermal flow sensor is factory installed in the en-

tering fluid nozzle to prevent operation without flow through

the cooler. See Fig. 29. The flow sensor is factory wired.

Proper software configuration of the cooler pump control

parameters is required to prevent possible cooler freeze-up.

Refer to the Controls, Start-Up, Operation, Service and

Troubleshooting guide for more information.
BRINE UNITS — Special factory modifications to the units

are required to allow them to operate at fluid temperatures

less than 40 F (4.4 C). Be sure that the fluid has sufficient

inhibited glycol or other suitable corrosion-resistant anti-

freeze solution to prevent cooler freeze-up.
PREPARATION FOR YEAR-ROUND OPERATION — In

areas where the piping or unit is exposed to 32 F (0

 C) or

lower ambient temperatures, freeze-up protection is required

using inhibited glycol or other suitable corrosion-resistant anti-

freeze solution and electric heater tapes. Heater tapes on piping

should have a rating for area ambient temperatures and be cov-

ered with a suitable thickness of closed-cell insulation. Route

power for the heater tapes from a separately fused disconnect.

Mount the disconnect within sight from the unit per local or

NEC (National Electric Code) codes. Identify disconnect at

heater tape power source with a warning that power must not

be turned off except when servicing unit.

A drain connection is located at the bottom of the cooler

head. See Fig. 2-14 for connection location. Install shut-off

valves to the drain line before filling the system with fluid.

T1

T2

PP

PP

D

V

Heater (Optional)

Chilled Water Out

Chilled Water In

FS

LEGEND

D

Drain,

3

/

4

-in. NPT

FS

Flow Switch

PP — Pipe Plug,

1

/

4

-in. NPT

T1

Leaving Water Thermistor

T2

Entering Water Thermistor

V

Vent,

1

/

4

-in. NPT

Fig. 28 — Typical Piping Diagram on 30XA Units without Hydronic Package

a30-4416

20 Mesh Stainer

20 Mesh Strainer

IMPORTANT: Automatic vents should be located in

accessible locations for maintenance purposes and

protected from freezing.

WARNING

Applications that utilize fresh water as the circulated fluid

require that the circulating pump be controlled directly by

the chiller. Operation with fresh water is not fail-safe

should there be a loss of power to the chiller or to the circu-

lating pump. Freeze damage due to power loss or disabling

chiller pump control in fresh water systems will impair or

otherwise negatively affect the warranty.

IMPORTANT: Adding antifreeze solution is the only

certain means of protecting the unit from freeze-up if

heater fails or electrical power is interrupted or lost

while temperatures are below 32 F (0

 C).

Fig. 29 — Thermal Flow Sensor

a30-3432

Advertising