Carrier AQUAFORCE 30XA080-500 User Manual

Page 61

Advertising
background image

61

PUMP MODIFICATION/TRIMMING — Since the pumps

are constant speed, the only way to obtain greater flow with a

given pump/impeller is to decrease system head. This will

allow the pump to “ride” its curve to the right, resulting in

increased flow. If greater flow is necessary, consider opening

the combination valve. Also, verify that the strainer is clean,

and that no unnecessary system resistance is present, such as

partially closed isolation valves.

Once the combination valve is set, note the stem position. If

later service work requires the valve to be closed, it will be easier

to re-balance the system, if the original balance point is known.

Increasing system resistance by closing the balancing valve

will force the pump to “ride” its curve to the left, resulting in

less flow. Although this does reduce power consumption

slightly, it may not be the desirable method of reducing the

flow, especially if a large reduction is needed.

The other method for reducing flow on a constant speed

pump is impeller trimming. The impellers in the pumps provid-

ed in the 30XA hydronic kit can be easily removed for this

purpose. Refer to the vendor literature packet supplied with the

hydronic package information on Seal Replacement in the

Service section, and follow instructions for impeller removal

and trimming. See Fig. 33 and 34 for pump envelope curve in-

formation. Trimming should only be done by a qualified ma-

chine shop that has experience in this operation. Contact your

local Carrier representative for a recommended machine shop.

Impeller trimming has the added benefit of maximum bhp

(brake horsepower) savings, which can recover the cost

incurred by performing the impeller trimming.
FREEZE PROTECTION — The 30XA units are provided

with a flow switch to protect against freezing situations that

occur from no water flow. While the flow switch is helpful in

preventing freezing during no-flow situations, it does not

protect the chiller in case of power failure during sub-freezing

ambient temperatures, or in other cases where water tempera-

ture falls below the freezing mark. Appropriate concentrations

of inhibited propylene or ethylene glycol or other suitable

inhibited antifreeze solution should be considered for chiller

protection where ambient temperatures are expected to fall

below 32 F (0° C). Consult local water treatment specialist on

characteristics of the system water and add a recommended

inhibitor to the chilled water. The Carrier warranty does not

cover damage due to freezing.

If the pump will be subjected to freezing temperatures, steps

must be taken to prevent freeze damage. If the pump will not

be used during this time, it is recommended to drain the pump

and hydronic package and these components are backflushed

with inhibited glycol. Otherwise, a glycol-water solution

should be considered as the heat transfer fluid. Drains are locat-

ed on the pump(s) and suction guide/strainer for units with hy-

dronic kits. Units without hydronic kits have a drain plug

mounted on the bottom of the cooler head at each end of the

cooler.
NOTE: Do not use automobile anti-freeze, or any other fluid

that is not approved for heat exchanger duty. Only use

appropriately inhibited glycols, concentrated to provide ade-

quate protection for the temperature considered.

Use an electric tape heater for the external piping, if unit

will be exposed to freezing temperatures.

Ensure that power is available to the chiller at all times,

even during the off-season, so that the pump and cooler heaters

have power. Also make sure that the piping tape heaters have

power.

On units with pump packages, a heater is supplied with the

hydronic package that will protect this section from freezing in

outdoor-air temperatures down to –20 F (–29 C), except in the

case of a power failure. The Carrier warranty does not cover

damage due to freezing.

All units are equipped with cooler heaters. Units are protect-

ed from freezing down to 0° F (–18 C) through the cooler heat-

ers and control algorithms. If the unit controls the chilled water

pump and valves, allowing flow through the cooler, the unit is

protected from freezing down to –20 F (–29 C). The Carrier

warranty does not cover damage due to freezing.
PREPARATION FOR WINTER SHUTDOWN — If the unit

is not operational during the winter months, at the end of cooling

season complete the following steps.

1. If the unit has optional heater tapes on the cooler and the

cooler will not be drained, do not shut off power discon-

nect during off-season shutdown. If the unit has optional

heater tapes on the cooler and the cooler is drained, open

the circuit breaker for the heater, CB-13 or shut off power

during off-season shutdown.

2. Draining the fluid from the system is highly recommend-

ed. If the unit is equipped with a hydronic package, there

are additional drains in the pump housing and strainer

that must be opened to allow for all for all of the water to

drain.

3. Isolate the cooler from the rest of the system with water

shutoff valves.

4. Replace the drain plug and completely fill the cooler with

a mixture of water and a suitable corrosion-inhibited anti-

freeze solution such as propylene glycol. The concentra-

tion should be adequate to provide freeze protection to

15° F (8.3° C) below the expected low ambient tempera-

ture conditions. Antifreeze can be added through the vent

on top of the cooler. If the unit has a hydronic pump pack-

age, the pump must be treated in the same manner.

5. Leave the cooler filled with the antifreeze solution for the

winter, or drain if desired. Be sure to deenergize heaters

(if installed) as explained in Step 1 to prevent damage.

Use an approved method of disposal when removing anti-

freeze solution.

At the beginning of the next cooling season, be sure that

there is refrigerant pressure on each circuit before refilling

cooler, add recommended inhibitor, and reset the CB-HT (cir-

cuit breaker heater) (if opened) or restore power.

CAUTION

After trimming, the impeller MUST be balanced. Failure to

balance trimmed impellers can result in excessive vibra-

tion, noise, and premature bearing failure.

CAUTION

Failure to remove power before draining heater equipped

coolers and hydronic packages can result in heater tape and

insulation damage.

Advertising