Table 7 — 30XA140-500 Electrical Data, Single Point (High Ambient Option) (cont)

LEGEND

NOTES:

1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-

minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.

2. Cooler heater is wired into the control circuit so it is always operable as long as the

control power supply disconnect is on, even if any safety device is open.

3. For MCA that is less than or equal to 380 amps, 3 conductors are required.

For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.

4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.

a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)

to 500 kcmil.

b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is

3/0 to 500 kcmil.

c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps

is 1/0 to 500 kcmil.

d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps

is 250 kcmil to 500 kcmil.

5. Data provided circuit 1/circuit 2 where there are two circuits.

UNIT

30XA

UNIT VOLTAGE

NUMBER

OF

COND

FANS

10 HP PUMP, 3450 RPM

15 HP PUMP, 3450 RPM

CONTROL CIRCUIT

V-Hz

(3 Ph)

Supplied

MCA

MOCP

ICF

Rec

Fuse

Size

MCA

MOCP

ICF

Rec

Fuse

Size

Voltage

1 PH,

60 Hz

MCA

and

MOCP

Min

Max

WD

XL

WD

XL

140

230-60

207

253

10

592.4

800

869.3

700

607.0

800

883.9

700

115

40

200-60

187

220

10

652.4

800

986.5

800

668.6

800

1002.6

800

115

40

460-60

414

506

10

296.2

400

434.7

1066.7

350

303.5

400

442.0

1074.0

350

115

40

575-60

518

633

10

228.4

300

344.6

850.6

300

234.3

300

350.5

856.5

300

115

40

380-60

342

418

10

346.7

450

523.0

1288.0

400

355.5

500

531.9

1296.9

400

115

40

160

230-60

207

253

10

673.1

800

1067.1

800

687.7

800

1081.7

800

115

40

200-60

187

220

10

740.5

1000

1213.0

1000

756.6

1000

1229.1

1000

115

40

460-60

414

506

10

335.7

450

533.2

1341.2

400

343.0

450

540.5

1348.5

400

115

40

575-60

518

633

10

259.4

350

424.3

1070.3

300

265.2

350

430.1

1076.1

300

115

40

380-60

342

418

10

393.3

500

641.2

1620.2

450

402.1

500

650.0

1629.0

450

115

40

180

230-60

207

253

12

115

40

200-60

187

220

12

115

40

460-60

414

506

12

115

40

575-60

518

633

12

115

40

380-60

342

418

12

115

40

200

230-60

207

253

12

115

40

200-60

187

220

12

115

40

460-60

414

506

12

115

40

575-60

518

633

12

115

40

380-60

342

418

12

115

40

220

230-60

207

253

13

115

40

200-60

187

220

13

115

40

460-60

414

506

13

115

40

575-60

518

633

13

115

40

380-60

342

418

13

115

40

240

230-60

207

253

13

115

40

200-60

187

220

13

115

40

460-60

414

506

13

115

40

575-60

518

633

13

115

40

380-60

342

418

13

115

40

260

460-60

414

506

15

115

40

575-60

518

633

15

115

40

380-60

342

418

15

115

40

280

460-60

414

506

16

115

40

575-60

518

633

16

115

40

380-60

342

418

16

115

40

300

460-60

414

506

16

115

40

575-60

518

633

16

115

40

380-60

342

418

16

115

40

325

460-60

414

506

18

115

40

575-60

518

633

18

115

40

380-60

342

418

18

115

40

350

460-60

414

506

18

115

40

575-60

518

633

18

115

40

380-60

342

418

18

115

40

400

460-60

414

506

20

115

50

575-60

518

633

20

115

50

380-60

342

418

20

115

50

450

460-60

414

506

22

115

50

575-60

518

633

22

115

50

380-60

342

418

22

115

50

500

460-60

414

506

22

115

50

575-60

518

633

22

115

50

380-60

342

418

22

115

50

ICF

Instantaneous Current Flow

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
WD

Wye-Delta

XL

Across-the-Line

Advertising