Table 8 — 30XA140-500 Electrical Data, Dual Point (High Ambient Option) (cont)

LEGEND

NOTES:

1. Units are suitable for use on electrical systems where voltage supplied to the unit

terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.

2. Cooler heater is wired into the control circuit so it is always operable as long as the

control power supply disconnect is on, even if any safety device is open.

3. For MCA that is less than or equal to 380 amps, 3 conductors are required.

For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.

4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.

a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)

to 500 kcmil.

b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is

3/0 to 500 kcmil.

c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps

is 1/0 to 500 kcmil.

d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps

is 250 kcmil to 500 kcmil.

5. Data provided circuit 1/circuit 2 where there are two circuits.

UNIT

30XA

UNIT VOLTAGE

NUMBER

OF

COND

FANS

7.5 HP PUMP, 3450 RPM

10 HP PUMP, 3450 RPM

CONTROL CIRCUIT

V-Hz

(3 Ph)

Supplied

MCA

MOCP

ICF

Rec

Fuse

Size

MCA

MOCP

ICF

Rec

Fuse

Size

Voltage

1 PH,

60 Hz

MCA

and

MOCP

Min Max

WD

XL

WD

XL

140

230-60

207

253

6/4

383.8/235.1

600/350

660.8/414.4

450/300

383.8/242.3

600/350

660.8/421.6

450/300

115

40

200-60

187

220

6/4

422.6/259.0

700/400

756.7/473.4

500/300

422.6/266.9

700/400

756.7/481.4

500/350

115

40

460-60

414

506

6/4

191.9/117.5

300/175

330.4/207.2

962.4/578.2

225/150

191.9/121.1

300/175

330.4/210.8

962.4/581.8

225/150

115

40

575-60

518

633

6/4

147.7/ 90.7

225/125

263.9/165.6

769.9 /462.6 175/110

147.7/ 93.5

225/125

263.9/168.4

769.9/465.4

175/110

115

40

380-60

342

418

6/4

223.9/138.0

350/200

400.2/251.2

1165.2/700.2

300/175

223.9/142.4

350/200

400.2/255.5

1165.2/704.5

300/175

115

40

160

230-60

207

253

6/4

434.8/272.3

700/400

828.8/414.4

600/350

434.8/279.5

700/400

828.8/421.6

600/350

115

40

200-60

187

220

6/4

478.1/299.6

800/450

950.7/473.4

600/350

478.1/307.6

800/450

950.7/481.4

600/400

115

40

460-60

414

506

6/4

216.9/135.7

350/200

414.4/207.2

1222.4/578.2

300/175

216.9/139.3

350/200

414.4/210.8

1222.4/581.8

300/175

115

40

575-60

518

633

6/4

167.0/105.2

250/150

331.9/165.6

977.9/462.6

200/125

167.0/108.1

250/150

331.9/168.4

977.9/465.4

200/125

115

40

380-60

342

418

6/4

253.3/159.5

400/250

501.2/251.2

1480.2/700.2

300/200

253.3/163.8

400/250

501.2/255.5

1480.2/704.5

300/200

115

40

180

230-60

207

253

6/6

115

40

200-60

187

220

6/6

115

40

460-60

414

506

6/6

115

40

575-60

518

633

6/6

115

40

380-60

342

418

6/6

115

40

200

230-60

207

253

6/6

115

40

200-60

187

220

6/6

115

40

460-60

414

506

6/6

115

40

575-60

518

633

6/6

115

40

380-60

342

418

6/6

115

40

220

230-60

207

253

7/6

115

40

200-60

187

220

7/6

115

40

460-60

414

506

7/6

115

40

575-60

518

633

7/6

115

40

380-60

342

418

7/6

115

40

240

230-60

207

253

7/6

115

40

200-60

187

220

7/6

115

40

460-60

414

506

7/6

115

40

575-60

518

633

7/6

115

40

380-60

342

418

7/6

115

40

260

460-60

414

506

9/6

115

40

575-60

518

633

9/6

115

40

380-60

342

418

9/6

115

40

280

460-60

414

506

9/7

115

40

575-60

518

633

9/7

115

40

380-60

342

418

9/7

115

40

300

460-60

414

506

10/6

115

40

575-60

518

633

10/6

115

40

380-60

342

418

10/6

115

40

325

460-60

414

506

9/9

115

40

575-60

518

633

9/9

115

40

380-60

342

418

9/9

115

40

350

460-60

414

506

9/9

115

40

575-60

518

633

9/9

115

40

380-60

342

418

9/9

115

40

400

460-60

414

506

8/12

115

50

575-60

518

633

8/12

115

50

380-60

342

418

8/12

115

50

450

460-60

414

506

8/14

115

50

575-60

518

633

8/14

115

50

380-60

342

418

8/14

115

50

500

460-60

414

506

8/14

115

50

575-60

518

633

8/14

115

50

380-60

342

418

8/14

115

50

ICF

Instantaneous Current Flow

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
WD

Wye-Delta

XL

Across-the-Line

Advertising