Carrier AQUAFORCE 30XA080-500 User Manual

Page 47

Advertising
background image

47

GATE VALVE*

STRAINER*

VIBRATION
ELIMINATORS*

BALANCING VALVE/
SHUT OFF*

POWER
FD

FD
CONTROL

PRESSURE/
TEMPERATURE TAPS*

PUMP

DRAIN
SHUTOFF
VALVE

NOTES:

1. Chiller must be installed level to maintain proper compressor oil return.
2. Piping shown are general points-of-connection guides only and are not

intended for a specific installation. Wiring and piping shown are for a quick
overview of system and are not in accordance with recognized standards.

3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System

Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) handbook for details.

5. A 20 mesh strainer is required withinh 10 ft (3 m) of the cooler.

LEGEND

*Field-installed.

FD

Fused Disconnect

Airflow Through Condenser

Chilled Water Piping

Power Wiring

Fig. 19A — 30XA Typical Piping and Wiring (Units without Hydronic Package)

a30-4114

Fig. 19B — 30XA Typical Piping and Wiring (Units with Hydronic Package)

FIELD-SUPPLIED
FUSED DISCONNECT
CONTROL POWER

FIELD-SUPPLIED
FUSED DISCONNECT
UNIT POWER

AIRFLOW

DRAIN SHUTOFF VALVE

STRAINER*

GATE VALVE*

PUMP

PRESSURE/

TEMPERATURE

TAPS*

VIBRATION

ELIMINATORS*

BALANCING VALVE/

SHUTOFF*

NOTES:
1. Chiller must be installed level to maintain proper

compressor oil return and hydraulics.

2. Wiring and piping shown are general points-of-

connection guides only and are not intended for a
specific installation. Wiring and piping shown are
for a quick overview of system and are not in
accordance with recognized standards.

3. All wiring must comply with applicable local and

national codes.

4. All piping must follow standard piping techniques.

Refer to Carrier System Design Manual or appro-
priate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers)
handbook for details.

5. Air separator required as close to chiller as possi-

ble (except primary/secondary systems).

6. 20 mesh strainer required for open loop systems.

LEGEND

*Field-installed.

Airflow Through Condenser

Power Wiring

Chilled Water Piping