Carrier AQUAFORCE 30XA080-500 User Manual

Page 78

Advertising
background image

78

REFRIGERANT CHARGE

The liquid charging method is recommended for complete

charging or when additional charge is required.

The 30XA units are shipped from the factory with a full

charge of R-134a. The unit should not need to be charged at

installation unless a leak was detected in Step 6 — Leak Test

Unit section. If dehydration and recharging is necessary, use

industry standard practices or refer to Carrier Standard Service

Techniques Manual as required.

IMPORTANT: These units are designed for use with

R-134a only. DO NOT USE ANY OTHER refrigerant in

these units.

CAUTION

When charging, circulate water through the cooler at all

times to prevent freezing. Freezing damage is considered

abuse and may void the Carrier warranty.

CAUTION

DO NOT OVERCHARGE system. Overcharging results

in higher discharge pressure with higher cooling fluid con-

sumption, possible compressor damage, and higher power

consumption.