HPP-100 Hand-Held Programmer

Revision 3.3

10

Set the Unlock Time [N]

The Unlock Time is the amount of time that the Master Control Unit’s lock power relay is
energized, allowing access. This time can be set from 1 to 99 seconds.

Example . . . to set the unlock time to 5 seconds:

Press . . . [4] [0] [5] [SEND]

DOOR UNLOCK TIME

SECS: 0 5

Set the Held-Open Time [N]

The Held-Open Time is the maximum amount of time an alarmed door or gate may be
held open by someone entering that door or gate. This time can be set from 1 to 99
seconds.

Example . . . to set the held-open time to 10 seconds:

Press . . . [5] [1] [0] [SEND]

DOOR OPEN TIME

SECS: 1 0

Set the Close of Business Time [N]

The Close of Business (COB) time automatically locks or prevents access to a location at
one specific time on a daily basis. This time is set in a two digit, hours / minutes format.
Two digits are required for each entry; for example, 7:15 A.M. is coded as ‘07’ ‘15.’

The default COB time is 17:00 hours or 5 P.M. This time should be changed, as needed,
to meet your application. We recommend always having a COB time programmed to
avoid the possibility of leaving an access point open or unlocked.

If your application will not use the COB feature, it can be disabled by entering a time of
00:00 hours. If your application requires setting the COB to 24:00 hours (Midnight), enter
a time of 23:59 or 00:01 (one minute before or one minute after Midnight).