7.4.4 Valve Tuning

Each valve has two settings; a dead zone and gain setting. The dead zone relates to the smallest
amount of movement the valve can produce. The gain relates to the maximum speed at which
the valve can move the boom function.
A dead zone and gain parameter exists for each valve. Each valve may be tuned:

 Automatically (as part of the automatic install or retune).
 Automatically (one valve at a time).
 Manually.

Automatic Dead Zone Calibration:

In the Valve tab, select the
function that you wish to
calibrate.
Press the Deadzone button.

Press and hold the Automatic
Test button. Continue to hold it
until the display says “Test
Complete”.
This will automatically calibrate
the Deadzone value for that
function.
When the test is complete, press
the check to save the setting.