Automatic Gain Calibration:
Before tuning the gain setting, the dead zone for that function must be tuned. If the dead zone
tuning has not been completed, follow the instructions for tuning a dead zone.

In the Valve tab, select the function
that you wish to calibrate.
Press the Gain button.

Press and hold the Automatic Test
button. Continue to hold it until
the display says “Test Complete”.
This will automatically calibrate the
gain value for that function.
When the test is complete, press
the check to save the setting.