11 installation instructions – Perfect Aire 1PAMSH36-MZO4-16 Installation Manual User Manual

Page 12

Advertising
background image

11

INSTALLATION INSTRUCTIONS

(2) Install the panel

(3) Hang the air-in grid to the panel, then connect

the lead terminator of the swing motor and that

of the control box with corresponding terminators

on the body respectively.

(4) Relocate the air-in grid in the procedure of

reversed order, install the air-in grid.

CAUTIONS:

a. Align the swing motor on the panel to the water

receiver of the body properly. (Refer to Fig.23)

b. Hang the four fixed ropes of the main body to the

installation cover and the other three covers of

the swing motor: (Refer to Fig.23 )

c. Install the panel on the main body with bolt (M5 16)

and washer. (Refer to Fig.23)

d. Adjust the four panel hook screws to keep the panel

horizontal, and screw them up to the ceiling evenly.

e. Regulate the panel in the direction of the arrow in

Fig.11 slightly to fit the panel's center to the center

of the ceiling's opening. Confirm that hooks of

four corners are fixed well.

f. Keep fastening the screws under the panel hooks,

until the thickness of the sponge between the body

and the panel's outlet has been reduced to about

0.16~0.24 inches (4~6mm). The edge of the panel should contact

with the ceiling well. (Refer to Fig.24)

Do not over tighten the screw. (Fig.25)

If the gap between the panel and ceiling still

exists after fastening the screws, the

height of the indoor unit should be modified again.

You can modify the height of the indoor unit through

the openings on the panel's four corners, if the lift of

the indoor unit and the drainpipe is not influenced

(refer to Fig.26-right).

The installation cover of the swing motor must sink

into the corresponding water receiver.

Body

Panel foam 2

Ceiling

Panel foam

Air plate

Panel

Panel foam1

Panel sealing foam

Inlet air

Outlet air

Fig.24

Ceiling Leakage

Dew

Fig.25

Hexagon nut

Ceiling

Horizontal adjustment

Fig.26

(3) The installation of ventilation motor and
ventilation pipe (if necessary)

a. Using a tool to knock off the pre-punching hole.

(Refer to Fig.27)

b. Four screw hole reserved for installation.

(Refer to Fig.27 )

Fig.27

Four screw hole

Pre-punching hole

Cover

Steel rope

Swing motor installation cover

Drain side

Fig.23

2

3

1

Swing motor side

Bolt, washer

Drain side

Please operate according

to the direction of the arrow,

or it cannot be disassembled

when it is necessary.

4

3

Advertising