Air and moisture in the refrigerant system have undesirable effects as indicated below:

Pressure in the system rises.

Operating current rises.

Cooling or heating efficiency drops.

Moisture in the refrigerant circuit may freeze and block capillary tubing.

Water may lead to corrosion of parts in the refrigeration system.

Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested

and evacuated to remove any noncondensables and moisture from the system.

Air purging with vacuum pump

Preparation

Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units

have been properly connected and all wiring for the test run has been completed. Remove

the service valve caps from both the gas and the liquid side on the outdoor unit. Note that

both the liquid and the gas side service valves on the outdoor unit are kept closed at this

stage.

Pipe length and refrigerant amount:

Connective

pipe length

Less than

16.41 feet (5m)

More than

16.41 feet (5m)

Air purging

method

Use vacuum

pump.

Use vacuum

pump.

Additional amount of refrigerant to be charged

AIR PURGING

Air purging

21

When relocating the unit to another place,
perform evacuation using vacuum pump.
Make sure the refrigerant added into the air
conditioner is liquid form in any case.

Open the valve stem until it hits against the
stopper. Do not try to open it further.
Securely tighten the valve stem cap with a
Crescent Wrench and Service Valve Wrench.
Valve stem cap tightening torque (See
Tightening Torque Table in previous page ).

Outdoor

unit

Indoor

unit

Refrigerant

Flare nut

Stopper

Cap

Valve body

Packed valve

Half union

Gas side

Liquid side

A

C

D

B

Valve stem

Fig.65

Fig.66

Caution in handling the packed valve

0.212 oz/ft