12 installation instructions – Perfect Aire 1PAMSH36-MZO4-16 Installation Manual User Manual

Page 13

Advertising
background image

12

INSTALLATION INSTRUCTIONS

3. Drainage pipe installation

(1) Installation principle

(2) Drainage pipe selection

Capacity(x1000Btu)

12

2.4

18

4

24

6

30

7

36

8

42

10

48

12

60

14

Water flowrate(g/h)

Ensure at least 1/100 slope of the drainage

pipe.

Adopt suitable pipe diameter.

Adopt nearby condensate water discharge.

Before installing condensate water pipeline,

determine its route and elevation to avoid

intersection with other pipelines and ensure

slope is straight.

Support drain link per code.

The drainage pipe diameter shall not be smaller than the drain hose of indoor unit.

According to the water flowrate and drainage pipe slope to choose the suitable pipe, the

water flowrate is decided by the capacity of indoor unit.

Fig.28

(4) Water-pump drainage
The maximum lifting height is 29.5 inches.

7.9in.

39.4-59.1in.

29

.5

in

.