14

INSTALLATION INSTRUCTIONS

For the concentrated drainage pipe system, there should design a blowhole at the highest

point of main pipe to ensure the condensate water discharge smoothly.

The air outlet shall face down to prevent dirt entering pipe.

Each indoor system should be installed with it.

The installation should consider the convenience for future cleaning.

(5) Ventline setting

The length of lifting pipe should not exceed the pump head of indoor unit water pump.

Pump head of big four way cassette: 29.5 inches (750mm).

Pump head of compact four way cassette: 19.7 inches (500mm) (9k, 12k, 18k units).

The drainage pipe should be set down inclined after the lifting pipe immediately to avoid

wrong operation of water level switch.

Refer to the following picture for installation reference.

(4) Lifting pipe setting of indoor unit with water pump

Flexible pipe

11.8in. (300mm)

Hanger

A

A:Length of vertical pipe

5.9in. (150mm)

B: Lift height

the pump head of water pump

Down incline pipe

B

Plug

Ventline

Plug

Indoor unit

Indoor unit

Fig.32

Fig.33

If the indoor unit has high extra static pressure and without water pump to elevate the

condensate water, such as high extra static pressure duct unit, the water storage pipe

should be set to avoid converse flow or blow water phenomena.

(3) Water storage pipe setting

Indoor unit

More than 1.97in.(50mm)

More than 0.98in.(25mm)

Plug

Water storage pipe

Fig.31