Potter PFC-7500 Series User Manual

Page 13

Advertising
background image

9

6.6

PFC-7500 Series Power Requirements

During AC power failure, the PFC-7500 Series panels, and all auxiliary devices connected to the panels, draw their

power from the battery. All devices must be taken into consideration when calculating the battery standby capacity.

Below is a list of the power requirements of the PFC-7500 Series panels. Add the additional current draw of Potter

keypads, smoke detectors, and any other auxiliary devices used in the system for the total current required.

6.7

PFC-7500 Series Standby Battery Calculations

Standby Battery Power Calculations

Standby Current

Alarm Current

PFC-7500/PFC-7501 Panel

Relay Outputs 1-2 (ON)
Active Zone 1
Active Zones 2-5
521B/BXT Smoke Detectors
SLR-835B Smoke Detectors
Other 2-Wire Smoke Detectors

Bell Output (600mA Max.)

Qty __1___x
Qty ______x

Qty ______x
Qty ______x
Qty ______x
Qty ______x

50mA
30mA

3.3mA

4mA

0.070mA
0.070mA

0.1mA

______mA
______
______
______
______
______
______

______

Qty __1___
Qty ______x

Qty ______x
Qty ______x
Qty ______x
Qty ______x

50mA
30mA

3.3mA

4mA

0.070mA
0.070mA

0.1mA

______mA
______
______
______
______
______
______

______mA

TAM Trouble Annunciator Module

17mA ______

17mA ______

RA-7630 Remote Fire Command Center

Qty ______x

63mA ______

Qty ______x

92mA ______

RA-7692 Fire Security Command Keypad

Qty ______x

30mA ______

Qty ______x

70mA ______

ZA714 Zone Expansion Module

Active Zones (EOL Installed)

Qty ______x
Qty ______x

7mA

1.6mA

______
______

Qty ______x
Qty ______x

7mA

*2mA

______
______

ZA715 Zone Expansion Module

Active Zones (EOL Installed)

Smoke Alarms

Qty ______x
Qty ______x
Qty ______x

7mA
4mA

.1 mA

______
______
______

Qty ______x
Qty ______x
Qty ______x

7mA

*30mA

.1mA

______
______
______

SNM Style W Notification Module

Qty ______x

45mA ______

Qty ______x

76mA ______

Aux. Powered Devices on Terminals 7 and 6

Other than Keypads

______mA

______mA

Total Standby

Total Standby______mA x number of Standby Hours needed

Total Alarm

*

Based on 10% of active zones in alarm

______mA
______ =
______mA

+

Total

Total Alarm _______mA

_________mA-hours
_________mA-hours
_________mA-hours
X 0.0001
= ________Amp-hrs Required

Advertising