21

AC

1

3

+B

5

BELL

6

SMK

11

Z1A+

7

RED

8

YEL

9

GRN

10

BLK

2

AC

4

-B

12

Z1A-

13

Z1B+

14

Z1B-

15

Z2+

16

Z2-

17

Z3+

18

Z3-

19

Z4+

20

Z4-

21

Z5+

22

Z5-

N/O

N/C COM

N/O

N/C COM

J11

1

2

3

4

J12

OUTPUT

2

OUTPUT

1

MAIN BACKUP

Telephone

Connections

J4

J5

Silence/Reset

Header

J13

Bell

Monitor

J14

Silence/Reset

Button

Silence/Reset

Push for 1 Second

Panel

Reset

J10 Trouble Annunciator Header

Relay Sockets for Optional

Form C Outputs on J11

PFC-7500 Series Commercial

Fire Panel

S

S

3.3K EOL

Zone 2

S

S

W

W

Zone 1

S

S

S

S

3.3K EOL

Zone 3

S

S

3.3K EOL

Zone 3

S

S

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

SNM Module

Normal/Silence Switch

Notification Circuit Module

Potter Model SNM

45mA @12 VDC

Remote DPDT

Relay

S = Supervised Circuit

S

S

The SNM Module must be

installed in the panel enclosure

connected by no more than 20

feet of conduit.

DPDT Relay

30mA coil operating

current at 12 VDC.

3.3K EOL

Normally Open

contacts will close

on alarm.

Normally Closed

contacts will Open

on alarm.

10K EOL Resistor

Wiring between the SNM Module

and the DPDT Relay is supervised

against open, shorts, and grounds.

Any of these trouble conditions will

cause the SNM Module's Bell

Trouble contacts to open.

S

S

The zone connected to

the Bell Trouble contacts

on the SNM Notification

Circuit Module must be

programmed as a

Supervisory Type zone.

22.10 Supervised Remote Relay