Power supply – Potter PFC-7500 Series User Manual

Page 23

Advertising
background image

19

22.4

SNM Class B Style W Multiple Notification Appliance Circuits

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

Potter Model SNM

45mA @ 12 VDC

The SNM Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

Panel Reset

AC

1

2

3

4

7

8

10 11 12 13

14 15 16

AC

B+

B-

9

RED

YEL

GRN BLK

Z1B-

Z2 -

Z2+

1

2

3

4

J12

Z1A- Z1B +

Z1A +

PFC-7500 Series Commercial Fire Command

Processor Panel

MAIN

BACKUP

J11

N/C COM N/O N/C COM N/

O

Telephone Connections

J10 Trouble Annunciator Header

5

6

BELL

SM K

O

U

TP

U

T

1

O

U

TP

U

T

2

SILENCE/RESET

PUSH FOR ONE SECOND

S ilence/Reset

B utton

S ilence/Reset

Header

17 18

Z3 -

Z3+

19 20

Z4 -

Z4+

21 22

Z5 -

Z5+

Bell

Monitor

r

J13

J14

Power Supply

J6

+ DC -

AC

Trouble

Batt

Trouble

J4

J3

J2

Green

LED

AC

AC

+ BAT -

Red

LED

DC

12 VDC @ 5 Amps

Battery

Start

TAM Module

Auxiliary Power Supply must be regulated, power

limited, and listed for Fire Protective Signaling

Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used,

terminals 3 and 4 can be jumpered together to

supply Bell Power from the panel.

The Auxiliary Power Supply and Notification

Circuit Module trouble contact zone must be

programmed as a Supervisory Type zone.

MINUS 2

MINUS 1

+OUT 1

+IN 1

+IN 2

-AUD

+AUD

+OUT 2

10K EOLR

DSM-12/24 Module

10K EOLR

Listed, Polarized Notification Appliances

Sync module required

when using multiple

notification appliances

When using a separate power supply, the

maximum current is 3 Amps.

See the Notification Appliance section for a list of appliances.

The Bell Output

programming for Fire

type zones must be set

to Steady.

The maximum voltage drop

between the panel Bell Output and

the Model 308 is .5 VDC when a

separate power supply is not used.

Regulated

12 VDC