Class b (style a) fire zones – Potter PFC-7500 Series User Manual

Page 15

Advertising
background image

11

11.1

Description

Terminals 15 to 22 are the Class B (Style A) fire zones on the PFC-7500 Series panels. These zones are suitable for

connecting powered or non-powered fire devices. For programming purposes, these zones are designated 2 to 5. The

maximum line impedance is 100 Ohms. The zone configurations on terminals 15 to 22 are described below:

Terminal

Function

Terminal

Function

15

Zone 2 voltage sensing

16

Zone 2 negative

17

Zone 3 voltage sensing

18

Zone 3 negative

19

Zone 4 voltage sensing

20

Zone 4 negative

21

Zone 5 voltage sensing

22

Zone 5 negative

11.2

Operational Parameters

The Class B (Style A) zones on the PFC-7500 Series panels can detect three conditions: open, normal, and short. Each

zone terminates with a Model 309, 3.3k Ohm EOL resistor (provided with the panel) and is rated for 53mA at 12 VDC.
The compatibility identifier for use with 2-wire smoke detectors is: A.

11.3

Zone Response Time

A condition must be present on the zone for at least 500 milliseconds before it is detected by PFC-7500 Series panels.

Only use detection devices that are rated for use with this delay.

11.4

Compatible 2-Wire Smoke Detectors

The table below lists detectors meeting the compatibility requirements for use with the Class B (Style A) zones on the

PFC-7500 Series fire panels. Do not mix detectors from different manufacturers on the same zone.

Manufacturer

Model

Detector

ID

Base

Base ID

# of

Detectors

Detection Systems

DS250

B

MB2W

A

10

Detection Systems

DS250TH, DS250HD

B

MB2W, MB2WL

A

10

Detection Systems

DS282, DS282TH

B

10

Hochiki

SLK-12

HD-4

HSB-12-1, HSB-12-1N

HB-80

20

Potter/Hochiki

SLK-835, SLK-835H

HD-5

HSB-200, HSB-200N

HB-55

7

Potter/Hochiki

SLR-835

HD-3

NS6-100

HB-55

7

Potter/Hochiki

SLR-835B

HD-6

7

Sentrol/ESL

429AT, 521B, 521BXT

S09A

12

System Sensor

1100, 1400

STD

10

System Sensor

1151

STD

B110LP

10

System Sensor

1451, 2451TH

STD

B401, B401B

10

System Sensor

1451DH

STD

DH400

10

System Sensor

2100, 2100T

STD

10

System Sensor

2400, 2400AT,

2400AIT, 2400TH

STD

10

System Sensor

2451

STD

B401, B401B, DH400

10

Class B (Style A) Fire Zones