Wiring diagrams, 1 snm with nac extender – Potter PFC-7500 Series User Manual

Page 20

Advertising
background image


16

22.1

SNM with NAC Extender

1K EOLR

1K EOLR

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

Potter Model SNM

45mA @ 12 VDC

The SNM Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

See the SNM

Installation Sheet

To panel terminal 7

To panel zone

To panel terminal 10

To panel zone

To panel alarm output

The Bell Output programming for Fire type zones must be set to Steady

NAC Extender

See installation sheet for

detailed connection

instructions

Note: Terminals 3

and 4 jumper together

to supply Bell Power

from the panel

Wiring Diagrams