California state fire marshal specifications – Potter PFC-7500 Series User Manual

Page 19

Advertising
background image

15

20.5

Remote Station Protective Signaling Systems

60 hours of standby battery must be provided. Up to two 12 VDC, 7.0 Ah batteries may be used. See standby battery

calculations. The PFC-7500 may be used to provide two reversing polarity telephone connections instead of dual phone

lines. See the PFC-7500 Installation Instruction sheet for wiring details.

20.6

Remote Annunciators

At least one Model RA-7630 or RA-7692 Remote Annunciator must be used on the system. When using a RA-7692

keypad, install one the panel door as described in the RA-7692 installation guide.
When using a RA-7630 keypad, install the keypad using conduit within 20 feet of the panel.

20.7

Notification Appliances

The following table indicates approved 12 VDC notification appliances.

Wheelock Model No.

Description

No. of Appliances

MT-12/24

Multi-tone Horn

5

MB-G6-12

Bell, 6 inch

11

MB-G10-12

Bell, 10 inch

11

RSS-121575W-F

Strobe, 15/75 candela

3

RSSP-121575W-F

Strobe, w/retrofit plate

3

NS-121575W-F

Horn Strobe, 15/75 candela

3

SM-12/24-R

Sync Module, Single circuit,

DSM-12/24-R

Sync Module, Dual circuit

20.8 Cross Zoning

When using cross zoning, there must be a minimum of two detectors installed in each protected space and the detector

installation spacing must be 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA 72.

20.9

Ground Fault

For supervised circuits, ground fault is detected at 0 (zero) Ohms.

California State Fire Marshal Specifications

21.1

Bell Output Definition

The bell output of the Model PFC-7501 must be programmed to operate Temporal for fire alarms.