4 lightning protection, 5 keypads – Potter PFC-7500 Series User Manual

Page 8

Advertising
background image


4

3.3

PFC-7500 Wiring Diagram

The PFC-7500 system below shows some of the accessory devices for use in various applications.

AC

1

3

+B

5

BELL

6

SMK

11

Z1A+

7

RED

8

YEL

9

GRN

10

BLK

2

AC

4

-B

12

Z1A-

13

Z1B+

14

Z1B-

15

Z2+

16

Z2-

17

Z3+

18

Z3-

19

Z4+

20

Z4-

21

Z5+

22

Z5-

N/O

N/C COM

N/O

N/C COM

J11

1

2

3

4

J12

OUTPUT

2

OUTPUT

1

MAIN BACKUP

Telephone

Connections

J4

J5

Silence/Reset

Header

J13

Bell

Monitor

J14

Silence/Reset

Button

Silence/Reset

Push for 1 Second

Panel

Reset

J10 Trouble Annunciator Header

Relay Sockets for Optional

Form C Outputs on J11

RE

D

BL

AC

K

G

RE

EN

Up to 500mA auxiliary current at 12 VDC from terminal 7

BL

AC

K

YE

LL

O

W

RE

D

GROUND

Cold Water Pipe

E arth Ground

Output Header J11

Two Form C (SPDT) Outputs.

Zo

ne

2

Output Header J12

Four Open Collector Outputs.

50mA at 30 VDC resistive

Zone 1

M

M

Direct connect to

unswitched 120 VAC 60 Hz

Secondary Power Supply

12 VDC

1.2 Amps Max. charging current.

Zone 5

Output 1 Output 2

W

W

Zo

ne

3

S

S

TAM

Trouble

Annunciator

Module

Model WLT

16.5 VAC 40VA

wire-in transformer

3.3k

Ohm

EOLR

Zo

ne

3

H

S

Keypad

Model RA-7630

For sprinkler supervision,

Normally Open devices

must be used.

Zone 2

3.3k Ohm

Zone 4

3.3k Ohm

Zone 3

3.3k Ohm

Al outputs must be

connected to devices

located within the same

room as the panel.

Heat detectors, pull stations, or any other contact devices listed

for Fire Protective Signaling can be connected to zones 1 to 5.

Zones 2 to 5 compatibility identifier: A

Maximum operating range: 8.8 to 14.2 VDC.

S

S

S

S

S

S

S

S

S

S

S

S

S

= Supervised Circuit

5 Zone LED Keypads

Keypad

Model RA-7692

30mA at 8 to 16 VDC.

63mA at 8.5 to 14 VDC

POWER

TROUBLE

ALARM

COMMAND

1

2

3

4

5

6

7

8

9

0

ABC

DEF

GHI

JKL

MNO

PQR

STU

VWX

YX

ENABLE

SILENCE

RESET

TEST

DRILL

Fire Command Center

S

S

S

S

S

S

POWER LIMITED

All circuits on the Model PFC-7500 comply

with the requirements for inherent power

limitation and are Class 2 except the

red battery wire.

WARNING

THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM

VERIFICATION FEATURE THAT RESULTS IN DELAY OF THE SYSTEM

ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL

DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT

EXCEED 60 SECONDS. NO OTHER SMOKE DETECTORS SHALL BE

CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE

LOCAL AUTHORITY HAVING JURISDICTION.

All zones are supervised

USE MARKING

Commercial Protected Premises

Control Unit

TYPES OF SERVICE

Central Station DACT, Remote Station Signaling Service, Suitable for

manual fire alarm, automatic fire alarm, sprinkler supervisory or

waterflow alarm.

Figure 2: PFC-7500 Wiring Diagram

3.4

Lightning Protection

Metal Oxide Varistors and Transient Voltage Suppressors on the panel help protect against voltage surges on

input and output circuits of the PFC-7500 Series panels. Additional surge protection is available by installing the

Lightning Suppressors.

3.5

Keypads

You can connect the Models RA-7630 or RA-7692 keypads to the 4-wire keypad bus provided by the panel on terminals

7, 8, 9, and 10. Do not use shielded wire for the keypad bus.

Advertising