17

22.2

SNM Class B Style W using Single Notification Appliance

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

Potter Model SNM

45mA @ 12 VDC

The SNM Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

Panel Reset

AC

1

2

3

4

7

8

10 11 12 13

14 15 16

AC

B+

B-

9

RED

YEL

GRN BLK

Z1B-

Z2 -

Z2+

1

2

3

4

J12

Z1A- Z1B +

Z1A +

PFC-7500 Series Commercial Fire Command

Processor Panel

MAIN

BACKUP

J11

N/C COM N/O N/C COM N/

O

Telephone Connections

J10 Trouble Annunciator Header

5

6

BELL

SM K

O

U

TP

U

T

1

O

U

TP

U

T

2

SILENCE/RESET

PUSH FOR ONE SECOND

S ilence/Reset

B utton

S ilence/Reset

Header

17 18

Z3 -

Z3+

19 20

Z4 -

Z4+

21 22

Z5 -

Z5+

Bell

Monitor

r

J13

J14

TAM Module

Note: Terminals 3 and 4 jumperetogether to

supply Bell Power from the panel.

Listed, Polarized

Notification Appliance

10K EOLR

The Bell Output programming for Fire type

zones must be set to Temporal.

See the Notification Appliance section

for a list of appliances.

The maximum

voltage drop

between the panel

Bell Output and the

EOLR is .5 VDC when

a separate power

supply is not used.

Only one notification appliance may be used when

not using a sync module.

Regulated

12 VDC