9 remote station reversing relay connection, Pfc-7500 series commercial fire panel – Potter PFC-7500 Series User Manual

Page 24

Advertising
background image


20

22.9

Remote Station Reversing Relay Connection

AC

1

3

+B

5

BELL

6

SMK

11

Z1A+

7

RED

8

YEL

9

GRN

10

BLK

2

AC

4

-B

12

Z1A-

13

Z1B+

14

Z1B-

15

Z2+

16

Z2-

17

Z3+

18

Z3-

19

Z4+

20

Z4-

21

Z5+

22

Z5-

N/O

N/C COM

N/O

N/C COM

J11

1

2

3

4

J12

OUTPUT

2

OUTPUT

1

MAIN BACKUP

Telephone

Connections

J4

J5

Silence/Reset

Header

J13

Bell

Monitor

J14

Silence/Reset

Button

Silence/Reset

Push for 1 Second

Panel

Reset

J10 Trouble Annunciator Header

Relay Sockets for Optional

Form C Outputs on J11

PFC-7500 Series Commercial

Fire Panel

+

-

+

-

Bl

ac

k

Re

d

S

Alternate Alarm

Combo Alarm

Auxiliary Power In

+ Signal Voltage In

+ To Remote Receiver

- To Remote Receiver

- Signal Voltage In

EARTH GROUND

GROUND
GROUND

Up to 60 hours of battery standby time can be supplied using two 7.7 Ah,

sealed, Lead-Acid batteries.

All modules must be installed in an enclosure connected by no more than 20

feet of conduit.

This configuration transmits alarm and trouble signals only and does not

transmit Supervisory signals.

For complete system reports, use the 2-line dialer capability of the panel.

Reversing Relay Module

Potter Model PFC-7500

5mA Standby, 55mA Alarm @12 VDC

Alternate Alarm

Combo Alarm

Auxiliary Power In

+ Signal Voltage In

+ To Remote Receiver

- To Remote Receiver

- Signal Voltage In

EARTH GROUND

GROUND
GROUND

Reversing Relay Module

Potter Model PFC-7500

5mA Standby, 55mA Alarm

@12 VDC

S

To Telephone Line

To Telephone Line

S = Supervised Circuit

Intended for connection to a

polarity reversal circuit of a

remote station receiving unit

having compatible ratings.

S

S

S

Fire Trouble Output 2

Fire Alarm Output 1

Note: Output 1 must be programmed as a Fire

Alarm Output and Output 2 must be

programmed as a Fire Trouble Output.