Panel specifications – Potter PFC-7500 Series User Manual

Page 5

Advertising
background image

1

1.1

Power Supply

Primary Power Input: 16.5 VAC 40 VA (Model WLT wire-in) or 12/24 VDC from Fire Alarm Control Panel (FACP)
Standby Battery: One or two 12 VDC batteries

Auxiliary Output: 500mA at 12 VDC
Bell Output: .6 Amps at 12 VDC (PFC-7501 only)
Smoke Detector Output: 100mA at 12 VDC (PFC-7501 only)
All circuits inherent power limited except the red battery wire.
* For Commercial Fire installations, see the Compliance Instructions section.

1.2

Communication

Built-in SDLC Digital Dialer communication to Potter Model SCS-1R Receivers.
Built-in CID communication to non-Potter (Contact ID) receivers.
Can operate as a local system (PFC-7501 only).

1.3

Panel Zones

One Class A (Style D) zone (terminals 11 to 14).
Four 3.3K Ohm EOL Class B (Style A) powered fire zones with reset capability (terminals 15 to 22).

1.4

Remote Annunciators (Alphanumeric or LED Keypads)

Connect RA-7630 keypads and LED keypads to the PFC-7500 Series keypad bus.

1.5

Auxiliary Outputs

Two Form C (SPDT) outputs (Outputs 1 and 2). Each output requires one Model 305 plug-in relay. Each relay is rated

for 1 Amp at 30 VDC.
Four open collector annunciator outputs (Outputs 1 to 4). No relay is required. Each output is rated for 50mA at 30

VDC resistive.

1.6

Push-Button Reset

The PFC-7500 Series panels each provide a push button mounted on the printed circuit board that allows authorized

users to reset latch detectors and silence active alarm bell outputs. See section 16.1.

1.7

Enclosure Specifications

The PFC-7500 Series panels are shipped in an enclosure with End-of-Line resistors, battery leads, User’s Guide

8910224, and Programming Sheet.

Size:

12.5” W x 9.5” H x 3.75” D

Weight:

4 lbs

Color:

Red

Construction:

20-gauge cold-rolled steel

Panel Specifications