14 | PIR Ready VT7200 Series-Installation Guide

seconds after changes are made, the display will resume automatic status display
scrolling.

To turn on the back light to high level, press any key on the front panel. The back lit
display will return to low level when the Terminal Equipment Controller is left unattended
for 45 seconds

Sequence of auto-scroll status display:

ROOM &

HUMIDITY

SYSTEM MODE

SCHEDULE

STATUS

OUTDOOR

TEMPERATURE

ALARMS

x.x °C or °F
XX % RH

Sys mode

Occupied

Outdoor

Service

Auto

x.x °C or°F

Filter

Sys mode
Cool

Stand-By

Window

Sys mode
heat

Unoccup

Outdoor air temperature

Display is only enabled when outdoor air temperature network variable is received.


Occupancy Status

Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling
display.


Alarms

If alarms are detected, they will automatically be displayed at the end of the status
display scroll.

During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.

Two alarms maximum can appear at any given time. The priority for the alarms is as
follows:

Two

status LED’s on the Terminal Equipment Control cover are used to indicate a call for

heat or a call for cooling.

Service

Indicates that there is a service alarm as per one of the configured binary
inputs ( BI2 )

Filter

Indicates that the filters are dirty as per one of the configured binary
inputs ( BI2 )

Window

Indicates that the outside window or door is opened and that the Terminal
Equipment Controller has cancelled any cooling or heating action ( BI1 )