St-By TM

Stand-by Timer value

Default 0.5 hours

Time delay between the moment where the PIR cover
detected the last movement in the area and the time which
the Terminal Equipment Controller stand-by mode and
setpoints become active.
Range is: 0.5 to 24.0 hours in 0.5hr increments

Unocc TM

Unoccupied Timer value

Default 0.0 hours

Time delay between the moment where the Terminal
Equipment Controller toggles to stand-by mode and the time
which the Terminal Equipment Controller unoccupied mode
and setpoints become active.
The factory value or 0.0 hours: Setting this parameter to its
default value of 0.0 hours disables the unoccupied timer.
This prevents the Terminal Equipment Controller to drift from
stand-by mode to unoccupied mode when PIR functions are
used
Range is: 0.0 to 24.0 hours in 0.5hr increments

St-By HT

Stand-by heating setpoint

Default value = 69 °F

The value of this parameter should reside between the
occupied and unoccupied heating setpoints and make sure
that the difference between the stand-by and occupied value
can be recovered in a timely fashion when movement is
detected in the zone.
Stand-by heating setpoint range is: 40 to 90 °F ( 4.5 to 32.0
°C )

St-By CL

Stand-by cooling setpoint limit

Default value = 78 °F

The value of this parameter should reside between the
occupied and unoccupied cooling setpoints and make sure
that the difference between the stand-by and occupied value
can be recovered in a timely fashion when movement is
detected in the zone.
Stand-by cooling setpoint range is: 54 to 100 °F ( 12.0 to
37.5 °C )

Unocc HT

Unoccupied heating setpoint

Default value = 62 °F

Heating setpoint range is:

40 to 90 °F ( 4.5 to 32.0 °C )

Unocc CL

Unoccupied cooling setpoint

limit

Default value = 80 °F

Cooling setpoint range is:

54 to 100 °F ( 12.0 to 37.5 °C )

heat max

Maximum heating setpoint

limit

Default value = 90 °F ( 32 °C )

Maximum occupied & unoccupied heating setpoint

adjustment. Heating setpoint range is:

40 to 90 °F ( 4.5 to 32.0 °C )

cool min

Minimum cooling setpoint limit

Default value = 54 °F ( 12 °C )

Minimum occupied & unoccupied cooling setpoint

adjustment. Cooling setpoint range is:

54 to 100 °F ( 12.0 to 37.5 °C )