22 | PIR Ready VT7200 Series-Installation Guide

Lockout
Keypad lockout levels
Default value = 0 No lock

USER KEY FUNCTIONS

LEVEL

0

1

2

NOT USED

3

4

5

Out1Conf
Output # 1 configuration
Default is: 4.0 (2 control
outputs, no changeover)

Defines the type of operation needed for Output #1 (BO1
& BO2)
2.0, will limit the number of sequences of operation
available from 0 to 3
Will enable heat/cool operation from the same output
( refer to wiring diagram )
4.0, can access all the sequences of operation from 0 to 5
Will enable heat/cool operation from different output
( refer to wiring diagram )

CntrlTyp
Control type for Triac models
Default is: Floating

Defines the type of control output for the type of valves
installed VT7200C10xx only
On/Off
is for normally opened or normally closed 24 VAC 2
position valves
Floating is for modulating 3 wires control of 24 VAC
floating valves

SeqOpera Sequence of
operation
Default is: Sequence #1

Single output application

(Out1Conf) = 2.0

Dual output application

(Out1Conf) = 4.0

0 = Cooling Only

Yes access

Yes access

1 = Heating only

Yes access

Yes access

2 = Cooling with Reheat

Yes access

Yes access

3 = Heating with Reheat

Yes access

Yes access

4 = Cool and Heat, 2 outputs

No access

Yes access

5 = Cool and Heat, 2 outputs
with Reheat

No access

Yes access

For single output applications, the system access is also limited if UI3 is configured for
local changeover COS, COC/NC or COC/NC.