27 | PIR Ready VT7200 Series-Installation Guide

RA/DA

Reverse acting or Direct

acting signal for Analog

output signals

VT72xxF5x00(x) models

only

Default value: DA signal

Changes the action of the analog outputs on the analog

models.

DA = Direct acting

0 to 100 % = 0 to 10 VDC

RA = Reverse acting

0 to 10 % - 10 to 0 VDC

Reheat
Sets the time base for the
reheat output if used
Default value: 0 = 15
minute

Sets the reheat output time base
Valid only if reheat sequences are enabled
0 = 15 minutes
1 =
10 seconds for Solid state relays

UI3 dis
Display supply or
changeover temperature

Used as diagnostic / service help to troubleshoot and diagnose
sensor operation
Only when UI 3 is configured as an analog input ( SS or COS )