Occupied setpoints adjustments

Unoccupied and stand-by setpoints adjustments

Setting of the stand-by and unoccupied setpoints is done through the network or through
configuration setup only.

Mode button menu sequence

Modes presented to the user are dependent on the sequence of operation selected.
Default mode is shown in bold when sequence of operation parameter is changed.

System mode function

PLEASE NOTE THAT: Default system mode of operation is dependent on sequence of
operation selected

Default mode is in bold when sequence of operation parameter is changed

The available mode can only be changed through the network since there is no local
mode access

SEQUENCE SELECTED

MODE MENU

0 = Cooling Only

Off - Cool

1 = Heating Only

Off - Heat

2 = Cooling With Electric Reheat

Off

– Auto – Heat – Cool

3 = Heating With Electric Reheat

Off - Heat

4 = Cooling and Heating ( 2 modulating outputs )

Off

Auto – Heat – Cool

5 = Cooling / Heating ( 2 modulating outputs) with
reheat

Off

Auto – Heat – Cool

I

NSTALLER

C

ONFIGURATION

P

ARAMETER

M

ENU

Configuration can be done through the network or locally at the Terminal Equipment
Controller.

To enter configuration, press and hold the middle button (°C/°F or Override) for
8 seconds.

If a password lockout is active, “Password” is prompted. Enter password value
using the “up” and “down” arrows and press the middle button again to gain

COOLING

MODE

HEATING

MODE

OFF

MODE

AUTO MODE

Setpoint presented to user is the setpoint from
the last action taken by the Terminal
Equipment Controller or the one currently in
use.

Both heating and cooling setpoints are
changed simultaneously while respecting the
minimum configured deadband

Cool XX.X

°F or °C

Heat

XX.X

°F or °C

No access

to setpoint

Cool XX.X °F or °C and Heat XX.X °F or °C

Both heating & cooling setpoints change

simultaneously