5 | PIR Ready VT7200 Series-Installation Guide

4.

(COS) Change over analog sensor: Used for hot / cold air / water change over
switching in 2 pipe systems.

Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.

If temperature is > 77 °F = Hot air / water present

If temperature is < 75 °F = Cold air / water present

5.

(SS) Supply air sensor monitoring: Used for supply air temperature
monitoring.

Only used for network reporting of the supply air temperature. Has no internal
function in the Terminal Equipment Controller.