9 | PIR Ready VT7200 Series-Installation Guide

Pressure dependent VAV cooling / heating with changeover: VT7200C5x00(x)
Floating actuator

Mandatory

Out1Conf = 2.0

CntrltTyp = Floating

FL time = as per
actuator


If heat / cool auto-
changeover
with a local
discharge air
temperature sensor set:

SeqOpera = 0
Cooling only

UI3 = COS

Pressure dependent VAV cooling / heating with changeover: VT7200F5x00(x)
Analog actuator

Mandatory

Out1Conf = 2.0

RA/DA = as per
actuator


If heat / cool auto-
changeover
with a local
discharge air
temperature sensor set:

SeqOpera = 0
Cooling only

UI3 = COS

Supply air

temperature sensor

UI3 COS

0 V~ Com

24 V~ Hot

BO1 Open

BO2 Close

Changeover

Sensor

Room Temperature Control

& Maximum

Position

the actuator

Modulating Floating

VAV Actuator

0 to 10 VDC

Analog Actuator

Changeover

Sensor

Room Temperature Control

Minimum

& Maximum

Adjusted on the actuator

Position

Supply air

temperature sensor

0 to 10

VDC

UI3 COS

0 V~ Com

24 V~ Hot

AO1

Minimum
Adjusted on