17 | PIR Ready VT7200 Series-Installation Guide

access to all configuration properties of the Terminal Equipment Controller.
Entering a wrong password will prevent local access to the configuration menu.

Press the same middle button repetitively to scroll between all the available
parameters.

Use the up and down key to change the parameter to the desired value.

To acknowledge and save the new value, press the middle button again.

The next parameter will now be displayed.

Configuration interface

CONFIGURATION

PARAMETERS

DEFAULT VALUE

SIGNIFICANCE AND ADJUSTMENTS

PswrdSet
Configuration parameters
menu access password
Default value = 0
Range is: 0 to 1000

This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000

Com Addr
Terminal Equipment
Terminal Equipment Controller
networking address
Default value = 254
Range is: 0 to 254

Conditional parameter to

BACnet™ MS-TP models

VT7200X5x00B

Conditional parameter to Wireless models
VT7200X5x00W

For

BACnet™ MS-TP models, the valid range is

from 1 to 127. Default value of 254 disables
BACnet™ communication for the Terminal
Equipment Controller.
For wireless models, the valid range is 0 to 254
with a maximum of 30 Terminal Equipment
Controller per VWG


Pressing repetitively will individually scroll all the available parameters

Adjust / rotate parameter value down

Adjust / rotate parameter value up