SECTION 1.5

INTRODUCTION TO TROUBLESHOOTING

Rotor Rotational Speed

L

"NP" series generators are equipped w ith a 4-pole

Rotor. That is, the Rotor has tw o south m agnetic poles

and tw o north m agnetic poles. A 4-pole Rotor m ust be

operated at 1800 rpm to obtain a 60 Hertz AC output
frequency. The follow ing form ulas apply w hen calculat­
ing frequency, rpm and num ber of Rotor poles:

Hertz = RPM

X

No. of Rotor Poles

2 x 6 0

RPM =

2

X

60

X

Hertz

No. of =

Poles

No. of Rotor Poles

2 X 60 X Hertz

RPM

Voltage and Frequency

The generator's solid state Voltage Regulator w ill

m aintain an AC output voltage that is at a fixed ratio to
frequency. For exam ple, at a frequency of 60 Hertz, AC
output voltage w ill be m aintained at about 120/240 volts
(plus or m inus 2%). Should frequency drop to 30 Hertz,

voltage w ill decrease proportionally to about 60/120

volts.

For generators rated 120/240 volts, the engine gover­

nor should be set to m aintain a NO-LOAD frequency of
about 60.5-63.5 Hertz. The Voltage Regulator should

then be set to m aintain a voltage of about 121-127 volts

(line-to-neutral); or 242-254 volts (line-to-line).

Stator AC Connection Systems

1-PHASE, DUAL W INDING TYPE:

Som e NP/IM series generators have dual AC

pow er w indings (Figure 3). Each w inding supplies a

120 volts AC output. W hen the tw o w indings are con­

nected in series (Figure 4), a 240 volts AC output
results.

W hen installed, the unit m ay have ben connected to

supply a dual voltage output (120 and/or 240 volts). This

is show n In Figure 4. A 3-w ire connection system Is
used. Stator leads No. 11 and 44 form the tw o "hot"

leads; the Junction of stator leads 22 and 33 form the
"Neutral" lead. Notice the "Neutral" line is grounded.

A second alternative Is to connect the w iring to supply

120 volts AC only (Figure 5). W hen this connectior

m ethod Is used, a jum per w ire m ust be connected
betw een the tw o m ain circuit breakers (CB1 and CB2),

as show n.

PART 1

THE REVOLVING FIELD AC GENERATOR

Figure 3. The Dual Stator AC Pow er W indings

nnrowi fWtrCPi

,,

22

33

44

)CB.

‘f

CBzS

/

T2

(WHnE)

-120 V.----------------^

■ 120V.-

T1

(RED)

■ 24-3V.

T3

(BLACK)

Figure

4.

Connected for Dual Voltage AC Output

11

22 33 1------------------------------------

L 1

44 ------

K

1

T

T3

T2

r

1

(BLACK)

(WHITE)

T1
(RED)

I«----------------- 120 V.----------------

P

^----------------- -------------120V.--------------------------------- -------»

Figure 5. Connected for 120 Volts AC Output

PAGE 1.5-2