PARTI

THE REVOLVING FIELD AC GENERATOR

1

SECTION 1.6- TROUBLESHOOTING

(UNITS WITH 15 INCH STATOR)

Problem

3- Generator Produces High Voltage at No-Load

TESTIS- CHECK

BOTH

TEST 16-ADJUST

O.K.

VULi AuiC MHil/

FREQUENCY

1 la

HIGH

GOVERNOR

ADJUSTMENT

FREQUENCY GOOD,
VOLTAGE IS HIGH

L

TEST 17- CHECK

HIGH VOLTAGE

TESTS- REPLACE

AND ADJUST

CONDITION w

VOLTAGE REGULATOR,

VOLTAGE

TEST AND ADJUST

REGULATOR

CORRECTED

Problem 4- Voltage and Frequency Drop Low When Electrical Loads are Applied

TESTIS- CHECK

UNIT IS NOT

TEST 16-ADJUST

FOR

OVERLOAD

CONDITION

W

ENGINE

GOVERNOR

UNIT IS OVERLOADED

VOLTAGE/FREQUENCY

STILL DROP LOW

WHEN LOADS ARE

APPLIED

i

REDUCE LOAD TO UNIT’S

RATED WATTAGeAMPERAGE

CAPACITY

I O.K. NOW-

.. NOW Hii|

r

I^STOPTIST^

TEST 19- CHECK

CMr^lMC D/MAICn

AND CONDITION

REPAIR

NEEDED

PAGE 1.6-3