PARTI

THE REVOLVING FIELD AC GENERATOR

1

SECTION 1.7- TROUBLESHOOTING

(UNITS WITH 10 INCH STATOR)

Problem 3- Generator Produces High Voltage at No-Load

TEST 14- CHECK
AC VOLTAGE
AND FREQUENCY

FREQUENCY

O.K.

VOLTAGE IS HIGH

i

TEST 9- CHECK

VOLTAGE

REGULATOR

BOTH

■ ARE-

HIGH

I VOLTAGE IS STILL HIGHi

TESTIS

- ADJUST

ENGINE

GOVERNOR

FREQUENCY & VOLTAGE,

ARE BOTH GOOD NOW

GO TO PROBLEM 2

STOP

TESTS

Problem 4- Frequency and Voltage Drop Sharply When Load is Applied

UNIT IS OVERLOADED

i

REDUCE LOAD TO

WATTAGE/AMPERAGE
CAPACITY OF UNIT

TEST 17- CHECK

CnD n\/Ptai rtAH

NOT

TEST 15-ADJUST

ENGINE

.O.K.—

STOP

TESTS

CONDITION

LOADED

GOVERNOR

PROBLEM STILL EXISTS

1

I TEST 18- CHECK

ENGINE POWER

1 AND CONDITION

REPAIR
ENGINE

^ AS

NEEDED

PAGE 1.7-3