1 installation of sensor/transmitter – ENMET EN Series User Manual

Page 5

Advertising
background image

Sensor/Transmitter, Toxic Gas & Oxygen

ENMET Corporation

3


2.1 Installation of Sensor/Transmitter

1. ❏ Remove the cover, and mount the S/T in a location appropriate for the application. Use the enclosure mounting holes as

shown in Figure 2. The sensor faces down. Pay particular attention to the source and density of the target gas in choosing
the S/T location.

2. ❏ The hole in the left side wall of the S/T enclosure is sized to accommodate a liquid tight conduit fitting. Run conduit from

the S/T to the control. If intrinsically safe barriers are supplied, because the S/Ts are in a classified location, follow the
applicable electrical code provisions for intrinsically safe wiring. Run two wires through conduit. If the conduit is
metallic and does not contain other wiring likely to generate interference signals, unshielded insulated wires can be used.
Otherwise, use two wire shielded cable and ground the shield to the S/T enclosure. The S/T enclosure should be grounded
to earth ground for maximum RFI protection.

3. ❏ Connect the plus wire to TB1-1 and the minus wire to TB1-2 on the S/T circuit board, as shown in Figure 2.

C

AUTION

:

Before connecting S/T to C

ONTROL

remove the power source to C

ONTROL

. Failure to do so may cause damage to

sensitive components.

Figure 2: Sensor/Transmitter 4 – 20mA in NEMA-4 Package, Internal View

Figure 2a: Sensor/Transmitter 4 – 20mA in NEMA-4 Package, Internal View

4 – 20mA,

12 – 28VDC

Mounting Hole

2 places

Liquid Tight

Conduit

Fitting

TB1

Red LED

Sensor

Circuit Board

POTs: Gain and Zero

Note: No Zero pot in oxygen S/T

Test Points

NEMA-4 Aluminum Enclosure

shown without cover

4 – 20mA,

12 – 28VDC

Mounting Hole

2 places

Liquid Tight

Conduit

Fitting

TB1

Red LED

Sensor

Circuit Board

POTs: Gain and Zero

Note: No Zero pot in oxygen S/T

Test Points

NEMA-4 Aluminum Enclosure

shown without cover

Advertising