Chapter 2: Installing And Wiring Your Module

15

2. At each end of the cable, strip some casing to expose the individual

wires.

3. Trim the exposed signal wires to 2 in. lengths. Strip about 3/16 in.

(about 5 mm) of insulation away to expose the end of each wire.

4. At one end of the cable, twist the drain wire and foil shield together,

bend them away from the cable, and apply shrink wrap.

Insulation

Clear Wire

Black Wire

Foil Shield and Drain Wire

5. At the other end of the cable, cut the drain wire and foil shield back to

the cable and apply shrink wrap.

Insulation

Clear Wire

Black Wire

6. Connect the wires to the terminal block and field device as shown in

the following figures and table. The recommended maximum torque is
5 in-lb (0.565 Nm) for all terminal screws.

To guard against electrostatic damage and improve chassis grounding,

connect one of the shield pins on the terminal block of your module to
the chassis itself

Important: For CE compliance, Ferrite EMI Suppressors are needed

on each channel’s terminal block connection. Apply the suppressor
close to the module terminal block, as shown below. A Steward Part
28B2024-0A0 or equivalent is recommended. The Steward 28B2024-
0A0 has an impedance of 157

at 25 MHz, 256

at 100 MHz, and

can accommodate one turn of wire.