Spectrum Controls 1746sc-INI4vi User Manual

Page 33

Advertising
background image

Chapter 4: Using Your Input Module

29

Table 13. Input channel configuration word (O:e.0 through O:e.3)

Use these bit settings in the channel configuration word

To select…

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Input channel disable

0

Input channel enable

1

±

10 Vdc input range (-INI4vi only)

0

0

0

1–5 Vdc input range (-INI4vi only)

0

0

1

0–5 Vdc input range (-INI4vi only)

0

1

0

0–10 Vdc input range (-INI4vi only)

0

1

1

0–20 mA input range

1

0

0

4–20 mA input range

1

0

1

Invalid

1

1

0

Invalid

1

1

1

Engineering units

0

0

0

Scaled for PID

0

0

1

Proportional counts

0

1

0

1746-NI4 compatible format

0

1

1

User-defined scale A

1

0

0

User-defined scale B

1

0

1

Invalid

1

1

0

Invalid

1

1

1

Zero on open input circuit

0

0

Max. on open input circuit

0

1

Min. on open input circuit

1

0

Invalid

1

1

60 Hz input filter

0

0

50 Hz input filter

0

1

150 Hz input filter

1

0

500 Hz input filter

1

1

Auto-calibration disabled

0

Auto-calibration enabled

1

Unused

0

0

0

0

Invalid

1

1

1

1

Applies only to the 1–5 Vdc and 4–20 mA input ranges.

Advertising