Spectrum Controls 1746sc-INI4vi User Manual

Page 22

Advertising
background image

18

SLC 500

Isolated Analog Input Modules

Figure 2. Wiring schematic for 2-, 3-, and 4-wire analog inputs

Important:

Your module does

not provide power for analog inputs. Use a power supply

that matches the transmitter specifications.

Module channel

In +
Common -

Power +

Supply -

Transmitter

+ -

2-Wire Transmitter

Module channel

In +
Common -

Power +

Supply -

4-Wire Transmitter

Module channel

In +
Common -

Power +

Supply -

3-Wire Transmitter

Transmitter

Supply

Signal

GND

Transmitter

Supply

Signal

+ +

- -

Figure 3. Wiring schematic for single-ended analog inputs

Important:

With single-ended inputs, the channels are not isolated from each other.
Also, single-ended inputs are less immune to noise than differential inputs.

V in 0 +
I in 0 +
Common 0 -
Shield
Shield
V in 1 +
I in 1 +
Common 1 -
V in 2 +
I in 2 +
Common 2 -
Shield
Shield
V in 3 +
I in 3 +
Common 3 -

Power +

Supply -

Transmitter

+

Signal

Transmitter

+

Signal

Transmitter

+

Signal

Transmitter

Supply

Signal

GND

Input Module