Chapter 3: Things To Consider Before Using Your Module

25

Figure 9. Signal attenuation with 500 Hz input filter

0

-20

-40

-60

-80

-100

-120

-140

-160

-180

-200

0

500

1000

1500

2000

2500

3000 Hz

-3 dB

131 Hz

Amplitude (in dB)

Signal Frequency

Auto-Calibration Time

Your module requires some time to auto-calibrate a channel. During this
time, your module cannot sample and convert input signals. Table 10
shows the time required for auto-calibration. When enabled, auto-
calibration occurs every 10 seconds for each channel, independently.

Table 10. Auto-calibration time per channel
(based on filter frequency)

Filter Frequency

50 Hz

60 Hz

250 Hz

500 Hz

Current Input

182 ms

152 ms

39 ms

19.6 ms

Voltage Input (-INI4vi only)

508

430

108

56

Channel Enable And
Disable Times

Your module requires some time to enable or disable a channel. During
this time, your module cannot sample and convert input signals. Table 11
shows the time required for enabling or disabling a channel.

Table 11. Channel enable and disable times.

Duration

Channel Enable

Up to 6.5 ms
Enabling user-defined scaling may require an additional 0.1 ms.

Channel Disable

Up to 5.5 ms