36

SLC 500

Isolated Analog Input Modules

Table 15. Input channel status word (I:e.4 through I:e.7)

These bit settings in the status word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Indicate this

0

Input channel disabled

1

Input channel enabled

0

0

0

±

10 Vdc input range

0

0

1

1–5 Vdc input range

0

1

0

0–5 Vdc input range

0

1

1

0–10 Vdc input range

1

0

0

0–20 mA input range

1

0

1

4–20 mA input range

0

0

0

Engineering units

0

0

1

Scaled for PID

0

1

0

Proportional counts

0

1

1

1746-NI4 format

1

0

0

User-defined scale A

1

0

1

User-defined scale B

0

0

Zero on open input circuit

0

1

Max. on open input circuit

1

0

Min. on open input circuit

0

0

60 Hz input filter

0

1

50 Hz input filter

1

0

150 Hz input filter

1

1

500 Hz input filter

0

Auto-calibration disabled

1

Auto-calibration enabled

0

No error

1

Over-range error

0

No error

1

Under-range error

0

No error

1

Non-fatal channel error

0

No error

1

Fatal channel error

Advertising