SLC 500

Isolated Analog Input Modules

Troubleshooting

Figure 18. Problem resolution flowchart

Module

Status LED(s)

off.

Module fault

condition.

Check to see

that module is

seated properly

in chassis.

Cycle power.

Is problem

corrected?

Contact you local

distributor or

Spectrum

Controls.

Yes

No

End

Module

Status LED

on.

Check LEDs

on module.

Channel

Status LED(s)

blinking.

Channel

Status LED(s)

off.

Channel

Status LED(s)

on.

Channel is

not enabled.

Channel is

enabled and

working.

Enable channel if

desired by setting

channel config.

word (bit 0 = 1).

Retry.

End

Fault

condition.

Check channel

status word

bits 12–15.

Fatal channel error, such as
a software power-up failure
due to corrupt hardware or
malfunctioning software. Try
resetting the processor or
cycling power to your module.

Bit 15

set (1)

Non-fatal channel error, such
as an invalid configuration
word. Check the configuration
word. Correct and Retry.

Bit 14

set (1)

Low-range error. The input
signal is very near or below
the minimum limit for the
channel. Correct and Retry.

Bit 13

set (1)

High-range error. The input
signal is very near or above
the maximum limit for the
channel. Correct and Retry.

Bit 12

set (1)

Is problem

corrected?

Contact you local

distributor or

Spectrum

Controls.

No

Yes

End