Chapter 3: Things To Consider Before Using Your Module

23

Table 9. Channel update time
(based on number of channels enabled and filter frequency)

Filter Frequency

# of ch. enabled 50 Hz

60 Hz

250 Hz

500 Hz

Current Input

1

20.0 ms

16.6 ms

4.0 ms

4.1 ms

2

20.5

17.7

7.3

7.3

3

19.8

16.6

10.6

10.7

4

21.0

17.0

13.8

13.8

Voltage Input (-INI4vi only)

1

19.7 ms

16.6 ms

5.0 ms

5.0 ms

2

19.7

17.2

9.2

9.2

3

19.7

16.6

13.5

13.5

4

19.7

18.0

18.0

18.0

The 3 dB cut-off frequency is the frequency at which input signals are
passed with 3 dB of attenuation.

Choose a filter frequency so that the frequency of your fastest changing
signal is lower than that filter’s 3 dB cut-off frequency. All frequency
components above the 3 dB cut-off frequency are increasingly
attenuated, as shown in the following figures.

Figure 6. Signal attenuation with 50 Hz input filter

0

-20

-40

-60

-80

-100

-120

-140

-160

-180

-200

0

50

100

150

200

250

300 Hz

-3 dB

13.1 Hz

Amplitude (in dB)

Signal Frequency