31

Table 14. Data format definitions

Selected

Actual Signal Limits

Count Limits

Data Format

Input Range

Min.

Max.

Min.

Max.

Engineering Units

±

10 V

-10.25 V

+10.25 V

-10250

+10250

0–10 V

-0.50 V

+10.25 V

-500

+10250

0–5 V

-0.50 V

+5.50 V

-500

+5500

1–5 V

+0.50 V

+5.50 V

+500

+5500

0–20 mA

0.0 mA

+20.5 mA

0

+20500

4–20 mA

+3.5 mA

+20.5 mA

+3500

+20500

Scaled for PID

±

10 V

-10 V

+10 V

0

+16383

0–10 V

0 V

+10 V

0

+16383

0–5 V

0 V

+5 V

0

+16383

1–5 V

+1 V

+5 V

0

+16383

0–20 mA

0 mA

+20 mA

0

+16383

4–20 mA

+4 mA

+20 mA

0

+16383

Proportional Counts

±

10 V

-10.25 V

+10.25 V

-32768

+32767

0–10 V

-0.50 V

+10.25 V

-32768

+32767

0–5 V

-0.50 V

+5.50 V

-32768

+32767

1–5 V

+0.50 V

+5.50 V

-32768

+32767

0–20 mA

0.0 mA

+20.5 mA

-32768

+32767

4–20 mA

+3.5 mA

+20.5 mA

-32768

+32767

1746-NI4-

±

10 V

-10 V

+10 V

-32768

+32767

compatible

0–10 V

0 V

+10 V

0

+32767

0–5 V

0 V

+5 V

0

+16384

1–5 V

+1 V

+5 V

+3277

+16384

0–20 mA

0 mA

+20 mA

0

+16384

4–20 mA

+4 mA

+20 mA

+3277

+16384

User-defined

±

10 V

-10.25 V

+10.25 V

scale A (and B)

0–10 V

-0.50 V

+10.25 V

0–5 V

-0.50 V

+5.50 V

See note

.

1–5 V

+0.50 V

+5.50 V

0–20 mA

0.0 mA

+20.5 mA

4–20 mA

+3.5 mA

+20.5 mA

Provides direct compatibility with the 1746-NI4 module.

For user-defined scale A (or B ), the data in output words 4 and 5 (or 6 and 7) determine

the count limits. See the next subsection,

Setting The User-Defined Scale Limits, for

information on the User-Defined Scale data format .

Note: Modules marked Series B Revision 1.00 or earlier had different signal limits for the

Scaled for PID data format (see the Owner’s Guide that came with your module).