CAUTION: Never operate the HWG circulating

pump while dry. If the unit is placed in operation

before the hot water generator piping is

connected, be sure that the pump wires are

disconnected from the contactor.

Hot Water Generator Connections cont.

Hot Water Generator Startup

1. Make sure the power is off to the heat pump. Connect

the wire from the hot water generator pump to T1 on

the contactor.

2. Close the drain valve to the water heater.

3. Open the cold water supply to the tank.

4. Open a hot water faucet in the building to bleed air

from the system. Close when full.

5. Open the pressure relief valve to bleed any remaining

air from the tank, then close.

6. If so equipped, turn the venting (burping) screw in the

center of the pump two (2) turns open (water will drip out),

wait until all air is purged from the pump, then tighten the

plug. Use vent couplings to bleed air from the lines.

7. Carefully inspect all plumbing for water leaks and

correct as required.

8. Before restoring electrical supply to the water heater,

adjust the temperature setting on the tank.

• On tanks with both upper and lower elements,

the lower element should be turned down to

the lowest setting, approximately 100°F. The

upper element should be adjusted to 120°F to

130°F. Depending upon the specific needs of

the customer, you may want to adjust the upper

element differently.

• On tanks with a single element, lower the

thermostat setting to 120°F.

9. After the thermostat(s) is adjusted, replace the access

cover and restore electrical supply to the water heater.

10. Make sure that any valves in the hot water generator

circuit are open.

11. Turn on the unit to heating.

12. The HWG pump should be running. When the pump

is first started, turn the venting (burping) screw (if

equipped) in the center of the pump two (2) turns open

until water dribbles out, then replace. Allow the pump

to run for at least five minutes to ensure that water has

filled the circulator properly.

13. The temperature difference between the water entering

and leaving the hot water generator should be 5°F to

15°F. The water flow should be approximately 0.4 gpm

per ton of nominal cooling.

14. Allow the unit to heat water for 15 to 20 minutes to be

sure operation is normal.