Blower performance data cont, Variable speed ecm motor, Envision – WaterFurnace Envision2 User Manual

Page 24: Compact installation manual, Single speed, Dual capacity

Advertising
background image

24

ENVISION

2

COMPACT INSTALLATION MANUAL

Blower Performance Data cont.

Variable Speed ECM Motor

Single Speed

Model

Max
ESP

Blower

Size

Motor

hp

Airfl ow DIP Switch Settings

1

2

3

4

5

6

7

8

9

10

11

12

015

0.50

9 x 7

1/2

300

400

500

600

700

L

M

H

018

0.50

9 x 7

1/2

300

400

500

600

700

800

L

M

H

024

0.50

9 x 7

1/2

400

500

600

700

800

900

1000

1100

1200

L

M

H

030

0.50

9 x 7

1/2

400

500

600

700

800

900

1000

1100

1200

L

M

H

036

0.50

11 x 10

1/2

650

750

850

1000

1100

1200

1300

1400

1500

L

M

H

036

w/1hp*

0.75

11 x 10

1

800

1000

1100

1300

1500

1600

1800

L

M

H

042

0.50

11 x 10

1/2

650

800

900

1050

1150

1250

1350

1450

1550

L

M

H

042

w/1hp*

0.75

11 x 10

1

800

900

1000

1200

1400

1600

1700

1850

2000

2200

2300

2400

L

M

H

048

0.50

11 x 10

1/2

650

800

900

1050

1150

1250

1350

1450

1550

L

M

H

048

w/1hp*

0.75

11 x 10

1

800

900

1000

1200

1400

1600

1700

1850

2000

2200

2300

2400

L

M

H

060

0.75

11 x 10

1

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

070

0.75

11 x 10

1

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

3/16/12

Dual Capacity

Model

Max
ESP

Blower

Size

Motor

hp

Air Flow DIP Switch Settings

1

2

3

4

5

6

7

8

9

10

11

12

026

0.50

9 x 7

1/2

400

500

600

700

800

900

1000

1100

1200

L

M

H

038

0.50

11 x 10

1/2

650

750

850

1000

1100

1200

1300

1400

1500

L

M

H

038

w/1hp*

0.75

11 x 10

1

800

1000

1100

1300

1500

1600

1800

L

M

H

049

0.50

11 x 10

1/2

650

800

900

1050

1150

1250

1350

1450

1550

L

M

H

049

w/1hp*

0.75

11 x 10

1

800

900

1000

1200

1400

1600

1700

1850

2000

2200

2300

2400

L

M

H

064

0.75

11 x 10

1

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

072

0.75

11 x 10

1

800

950

1100

1300

1500

1750

1950

2100

2300

L

M

H

Factory settings are at recommended L-M-H DIP switch locations
M-H settings MUST be located within boldface cfm range
Lowest and Highest DIP switch settings are assumed to be L and H respectively
cfm is controlled within ±5% up to the maximum ESP
Max ESP includes allowance for wet coil and 1 in. MERV 4

3/16/12

Advertising