Blower Performance Data cont.

L

G

N

C

High Voltage
Connections

3/16 in.

1

2

3

4

5

G - Blue

Y1 - Red

AUX - Gray

C - Black

L - Orange
G - Green

N - Brown

Low Voltage

Connections 1/4 in.

L

G

N

C

1

2

3

4

5

AUX - Gray

G - Blue

Y1 - Red

Y2 - Tan

C - Black

L - Orange
G - Green

N - Brown

High Voltage
Connections

3/16 in.

Low Voltage

Connections 1/4 in.

CAUTION: Disconnect all power before
performing this operation.

Setting Blower Speed - 5-Speed ECM

5-speed ECM blower motors have fi ve (5) speeds of which
three (3) are selectable on single speed and four (4) are
selectable on dual capacity.

5-Speed ECM Motor Connections - Single Speed

5-Speed ECM Motor Connections - Dual Capacity

5-Speed ECM - Dual Capacity

Model

Motor

Speed

Motor

Tap

T’stat

Cnct.

Blower

Size

Motor

HP

Airfl ow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

026

High

5

W

9 x 7

1/2

1120

1109

1097

1082

1066

1055

1044

1028

1011

1001

991

932

839

-

-

-

Med High

4

Y2

1020

1006

991

980

968

950

932

922

911

894

876

849

812

-

-

-

Med

3

917

906

895

884

872

854

836

824

812

792

772

754

719

-

-

-

Med Low

2

Y1

836

824

812

794

776

765

754

735

715

703

691

653

631

-

-

-

Low

1

G

735

721

707

687

666

653

640

622

603

589

574

533

-

-

-

-

038

High

5

W

11 x 10

1/2

1530

1503

1476

1453

1429

1413

1397

1376

1355

1342

1329

1276

1231

1173

-

-

Med High

4

Y2

1413

1388

1363

1342

1321

1303

1285

1263

1240

1226

1212

1173

1016

946

-

-

Med

3

Y1

1355

1325

1294

1276

1258

1235

1212

1188

1164

1144

1123

982

909

883

-

-

Med Low

2

1336

1299

1261

1242

1222

1202

1181

1157

1132

1111

1090

937

874

830

-

-

Low

1

G

1243

1182

1121

1061

1000

964

928

856

784

744

703

647

592

-

-

049

High

5

W

11 x 10

1

1934

1910

1886

1871

1855

1827

1799

1780

1760

1747

1734

1700

1659

1617

-

-

Med High

4

1799

1783

1767

1744

1720

1693

1666

1649

1631

1617

1603

1560

1530

1492

-

-

Med

3

Y2

1694

1680

1666

1642

1617

1592

1567

1552

1537

1519

1500

1453

1421

1372

-

-

Med Low

2

Y1

1575

1560

1540

1520

1502

1487

1471

1448

1424

1409

1393

1351

1308

1266

-

-

Low

1

G

1454

1406

1358

1333

1308

1285

1261

1239

1217

1198

1179

1072

1002

988

-

-

064

High

5

W

11 x 10

1

2245

2360

2214

2315

2173

2290

2136

2275

2103

2250

2070

2032

1998

1957

1910

1825

Med High

4

Y2

2092

2073

2054

2035

2015

1995

1975

1958

1940

1922

1904

1880

1843

1806

1767

1728

Med

3

1951

1931

1910

1889

1868

1850

1831

1812

1793

1774

1755

1722

1688

1654

1612

1562

Med Low

2

Y1

1812

1796

1780

1761

1741

1718

1695

1682

1668

1651

1633

1591

1555

1518

1480

1433

Low

1

G 1682

1661

1640

1616

1591

1573

1555

1533

1510

1495

1480

1441

1400

1351

1316

1263

072

High

5

W

11 x 10

1

2472

2360

2435

2315

2393

2290

2349

2275

2306

2250

2271

2236

2189

2121

2033

1936

Med High

4

Y2

2271

2248

2225

2205

2184

2166

2147

2129

2110

2094

2078

2039

2011

1977

1930

1846

Med

3

2133

2115

2096

2072

2047

2030

2013

1996

1979

1965

1950

1909

1873

1837

1793

1748

Med Low

2

Y1

2008

1985

1962

1939

1915

1898

1880

1862

1843

1828

1812

1774

1742

1703

1669

1635

Low

1

G

1806

1784

1761

1742

1722

1696

1669

1656

1642

1625

1607

1564

1527

1490

1443

1404

Factory speed settings are in Bold
Air fl ow values are with dry coil and standard fi lter
For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg.
Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G). The “Y1” and “Y2” settings must be between the “G” and “W” settings.

3/16/12

Advertising