21

ENVISION

2

COMPACT INSTALLATION MANUAL

Blower Performance Data

PSC BLOWER MOTOR BODY

HIGH

LOW

MEDIUM

B

L

O

W

E

R

S

P

E

E

D

W

IR

E

Standard PSC Motor

Model

Blower

Spd

Blower

Size

Motor

HP

Airfl ow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

009

H

6 x 8

1/10

480

450

440

420

410

380

360

340

330

310

300

-

-

-

-

-

MH

440

410

400

380

370

350

330

310

300

280

270

-

-

-

-

-

ML*

395

370

360

340

330

310

290

280

270

250

240

-

-

-

-

-

L

325

310

300

280

270

250

240

230

220

210

200

-

-

-

-

-

012

H

6 x 8

1/10

480

450

440

420

410

380

360

340

330

310

300

-

-

-

-

-

MH*

440

410

400

380

370

350

330

310

300

280

270

-

-

-

-

-

ML

395

370

360

340

330

310

290

280

270

250

240

-

-

-

-

-

L

325

310

300

280

270

250

240

230

220

210

200

-

-

-

-

-

015

H

9 x 7

1/6

845

835

825

815

800

790

775

755

735

710

680

565

-

-

-

-

M

735

730

725

715

705

700

690

675

660

630

600

485

-

-

-

-

L

620

615

610

605

600

590

580

565

550

520

490

-

-

-

-

-

018

H

9 x 7

1/6

845

835

825

815

800

790

775

755

735

710

680

565

-

-

-

-

M

735

730

725

715

705

700

690

675

660

630

600

485

-

-

-

-

L

620

615

610

605

600

590

580

565

550

520

490

-

-

-

-

-

024

H

9 x 7

1/5

1085

1055

1030

1005

980

950

925

895

870

830

795

735

555

-

-

-

M

915

895

875

855

835

815

795

765

735

705

675

590

520

-

-

-

L

845

830

815

795

775

750

725

702.5

680

650

625

505

-

-

-

-

030

H

9 x 7

1/3

1290

1270

1245

1220

1190

1160

1125

1090

1055

1020

985

880

760

-

-

-

M

1100

1090

1075

1060

1045

1020

995

970

940

910

875

785

625

-

-

-

L

910

905

900

895

885

875

865

850

835

810

780

710

560

-

-

-

036

H

10 x 10

1/2

1665

1640

1610

1580

1550

1515

1480

1450

1415

1315

1215

1090

980

-

-

-

M

1465

1445

1425

1400

1375

1350

1325

1260

1190

1140

1090

990

890

-

-

-

L

1130

1115

1100

1090

1075

1035

995

965

930

895

860

795

730

-

-

-

042

H

10 x 10

1/2

2010

1975

1940

1905

1870

1825

1780

1735

1690

1640

1590

1470

1210

-

-

-

M

1670

1650

1630

1610

1590

1560

1530

1495

1460

1425

1390

1190

1080

-

-

-

L

1220

1215

1210

1295

1200

1180

1160

1130

1100

1060

1020

930

-

-

-

-

048

H

10 x 10

1/2

2010

1975

1940

1905

1870

1825

1780

1735

1690

1640

1590

1470

1210

-

-

-

M

1670

1650

1630

1610

1590

1560

1530

1495

1460

1425

1390

1190

1080

-

-

-

L

1220

1215

1210

1295

1200

1180

1160

1130

1100

1060

1020

930

-

-

-

-

060

H

11 x 10

1

2430

2400

2365

2330

2290

2255

2215

2180

2140

2095

2045

1945

1835

1715

1510

1330

M

2265

2235

2205

2175

2145

2110

2070

2035

2000

1960

1915

1825

1730

1605

1440

1260

L

2075

2050

2020

1995

1965

1940

1915

1885

1850

1820

1785

1720

1610

1505

1335

1175

070

H

11 x 10

1

2430

2400

2365

2330

2290

2255

2215

2180

2140

2095

2045

1945

1835

1715

1510

1330

M

2265

2235

2205

2175

2145

2110

2070

2035

2000

1960

1915

1825

1730

1605

1440

1260

L

2075

2050

2020

1995

1965

1940

1915

1885

1850

1820

1785

1720

1610

1505

1335

1175

3/16/12

Optional High Static PSC Motor

Model

Blower

Spd

Blower

Size

Motor

HP

Airfl ow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

024

H

9 x 7

1/3

1290

1270

1245

1220

1190

1160

1125

1090

1055

1020

985

880

760

-

-

-

M

1100

1090

1075

1060

1045

1020

995

970

940

910

875

785

625

-

-

-

L

910

905

900

895

885

875

865

850

835

810

780

710

560

-

-

-

030

H

9 x 7

1/2

1365

1340

1325

1305

1280

1250

1215

1180

1140

1100

1055

960

850

-

-

-

M

1040

1040

1035

1030

1020

1005

990

970

945

915

885

810

735

-

-

-

L

880

880

880

880

875

870

860

840

820

800

775

730

480

-

-

-

036

H

10 x 10

1/2

1930

1905

1875

1840

1805

1765

1725

1680

1635

1530

1425

1270

1150

1025

-

-

M

1635

1620

1600

1580

1555

1530

1505

1465

1425

1335

1240

1135

1035

775

-

-

L

1230

1230

1225

1215

1200

1165

1130

1095

1060

1035

1005

935

795

675

-

-

042

H

10 x 10

3/4

2115

2075

2035

1980

1920

1900

1880

1840

1795

1730

1660

1390

1225

1070

-

-

M

2005

1980

1950

1910

1865

1815

1765

1725

1685

1585

1485

1315

1140

1025

-

-

L

1860

1835

1805

1780

1750

1715

1675

1635

1590

1540

1490

1260

1115

980

-

-

048

H

10 x 10

3/4

2115

2075

2035

1980

1920

1900

1880

1840

1795

1730

1660

1390

1225

1070

-

-

M

2005

1980

1950

1910

1865

1815

1765

1725

1685

1585

1485

1315

1140

1025

-

-

L

1860

1835

1805

1780

1750

1715

1675

1635

1590

1540

1490

1260

1115

980

-

-

Factory settings are in Bold
Air fl ow values are with dry coil and 1 in. MERV 4.
For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500
fpm by 0.16 in. wg.
* Denotes setting for 265 V operation.

3/16/12

Setting Blower Speed - PSC

CAUTION: Disconnect all power before
performing this operation.

Advertising