Operating parameters cont, Dual capacity models, Envision – WaterFurnace Envision2 User Manual

Page 44: Compact installation manual, First stage operation, Second stage operation

Advertising
background image

44

ENVISION

2

COMPACT INSTALLATION MANUAL

Operating Parameters cont.

Dual Capacity Models

First Stage Operation

Entering Water

Temp °F

Water Flow

gpm/ton

Cooling -- No Hot Water Generation

Suction Pressure

psig

Discharge Pres-

sure psig

Superheat

Subcooling

Water Temp Rise

°F

Air Temp Drop

°F DB

30

1.5

105 - 120

140 - 155

20 - 35

9 - 17

17 - 21

17 - 23

3.0

100 - 115

115 - 130

20 - 35

9 - 17

8 - 12

17 - 23

50

1.5

125 - 140

205 - 225

12 - 20

8 - 14

17 - 21

17 - 23

3.0

120 - 135

180 - 200

12 - 20

8 - 14

8 - 12

17 - 23

70

1.5

135 - 145

280 - 290

10 - 16

8 - 14

16 - 20

17 - 23

3.0

133 - 143

250 - 260

10 - 16

8 - 14

9 - 13

17 - 23

90

1.5

142 - 152

345 - 355

8 - 12

8 - 14

14 - 20

17 - 23

3.0

140 - 150

330 - 340

8 - 12

8 - 14

8 - 12

17 - 23

110

1.5

152 - 158

405 - 435

8 - 12

8 - 14

14 - 20

17 - 23

3.0

148 - 153

390 - 420

8 - 12

8 - 14

8 - 12

17 - 23

Entering Water

Temp °F

Water Flow

gpm/ton

Heating -- No Hot Water Generation

Suction Pressure

psig

Discharge Pres-

sure psig

Superheat

Subcooling

Water Temp Drop

°F

Air Temp Rise

°F DB

30

1.5

76 - 84

270 - 285

8 - 12

3 - 10

5 - 9

12 - 16

3.0

80 - 88

275 - 290

8 - 12

3 - 10

3 - 7

14 - 18

50

1.5

100 - 115

280 - 310

10 - 14

3 - 10

7 - 11

18 - 22

3.0

105 - 120

290 - 315

10 - 14

3 - 10

5 - 9

20 - 24

70

1.5

135 - 150

310 - 325

12 - 16

3 - 10

8 - 12

24 - 28

3.0

140 - 155

315 - 330

12 - 16

3 - 10

6 - 10

22 - 30

90

1.5

155 - 165

330 - 370

12 - 16

3 - 10

8 - 12

24 - 28

3.0

160 - 170

340 - 380

12 - 16

3 - 10

6 - 10

22 - 30

110

1.5

3.0

NOTE: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.

Heating performance based on entering air temperature of 70º F DB.

2/15/12

Second Stage Operation

Entering Water

Temp °F

Water Flow gpm/

ton

Cooling -- No Hot Water Generation

Suction Pressure

psig

Discharge Pres-

sure psig

Superheat

Subcooling

Water Temp Rise

°F

Air Temp Drop

°F DB

30

1.5

115 - 125

150 - 170

20 - 35

10 - 17

17 - 22

17 - 23

3.0

105 - 120

130 - 145

20 - 35

10 - 17

8 - 10

17 - 23

50

1.5

130 - 140

215 - 235

12 - 20

8 - 14

16 - 22

17 - 23

3.0

128 - 138

190 - 210

12 - 20

8 - 14

8 - 12

17 - 23

70

1.5

138 - 148

280 - 310

10 - 16

10 - 16

15 - 21

17 - 23

3.0

136 - 146

250 - 280

10 - 16

8 - 14

7 - 13

17 - 23

90

1.5

145 - 155

350 - 380

9 - 14

10 - 16

14 - 20

17 - 23

3.0

143 - 153

320 - 350

9 - 14

8 - 14

6 - 10

17 - 23

110

1.5

145 - 155

420 - 450

9 - 14

10 - 16

14 - 20

17 - 23

3.0

143 - 153

405 - 435

9 - 14

8 - 14

6 - 10

17 - 23

Entering Water

Temp °F

Water Flow gpm/

ton

Heating -- No Hot Water Generation

Suction Pressure

psig

Discharge Pres-

sure psig

Superheat

Subcooling

Water Temp Drop

°F

Air Temp Rise

°F DB

30

1.5

73 - 85

270 - 305

8 - 14

3 - 10

6 - 10

15 - 21

3.0

77 - 90

280 - 315

8 - 14

3 - 10

4 - 8

17 - 23

50

1.5

97 - 110

290 - 325

10 - 16

3 - 10

9 - 13

22 - 28

3.0

102 - 115

300 - 335

10 - 16

3 - 10

7 - 11

24 - 30

70

1.5

130 - 145

320 - 355

13 - 19

3 - 10

10 - 14

30 - 36

3.0

135 - 150

325 - 360

13 - 19

3 - 10

8 - 12

32 - 38

90

1.5

150 - 160

350 - 390

13 - 19

3 - 10

10 - 14

30 - 36

3.0

155 - 165

365 - 405

13 - 19

3 - 10

8 - 12

32 - 38

110

1.5

3.0

NOTE: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.