208 Volt Operation

All 208/230 units are factory wired for 230 volt operation.

For 208 volt operation, the red and blue transformer wires

must be switched on terminal strip PS.

CAUTION: When installing a unit with a variable

speed ECM blower motor in 460/60/3 voltage,

a neutral wire is required to allow proper unit

operation.

General

Be sure the available power is the same voltage and phase

as that shown on the unit serial plate. Line and low voltage

wiring must be done in accordance with local codes or the

National Electric Code, whichever is applicable.

Power Connection

Connect the incoming line voltage wires to L1 and L2 of the

contactor for single-phase unit. Consult the Electrical Data

tables for correct fuse sizes.

Electrical Connections

For Aurora Base Control, set SW2-1, FP1, on the printed

circuit board for applications using a closed loop antifreeze

solution to 15°F [-9.4°C]. On applications using an open

loop/ground water system (or closed loop no antifreeze), set

this dip switch to 30°F [-1.1°C], the factory default setting.

(Refer to the Dip Switch Field Selection table).

Freeze Detection

Aurora Base Control Box